3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(52)CH Alert 1 mode setting (Un\G192, Un\G208, Un\G224, Un\G240)
CH Alert 2 mode setting (Un\G193, Un\G209, Un\G225, Un\G241)
CH Alert 3 mode setting (Un\G194, Un\G210, Un\G226, Un\G242)
CH Alert 4 mode setting (Un\G195, Un\G211, Un\G227, Un\G243)
Set the alert mode of alert 1 to 4.
For details on the alert function, refer to the following.
Page 194, Section 4.12
(a) Alert mode and alert set value
Any alert set value can be set in each alert mode of alert 1 to 4 selected in this setting. Set the alert set value 1
to 4 in the following buffer memory areas. Alert set values 1 to 4 respectively correspond to alert modes of alert
1 to 4.
(b) Setting range
The following table lists set values and setting ranges which are available for alert set values set in each alert
mode.
Buffer memory area name
Buffer memory address
Reference
CH1 CH2 CH3 CH4
CH Alert set value 1 Un\G38 Un\G70 Un\G102 Un\G134
Page 108, Section 3.4.2 (18)
CH Alert set value 2 Un\G39 Un\G71 Un\G103 Un\G135
CH Alert set value 3 Un\G40 Un\G72 Un\G104 Un\G136
CH Alert set value 4 Un\G41 Un\G73 Un\G105 Un\G137
Set
value
Alert mode Setting range of alert set value
0 (no alert)
1 Upper limit input alert Within the temperature measurement range of the set input range
( Page 96, Section 3.4.2 (12))
2 Lower limit input alert
3 Upper limit deviation alert
(-(full scale)) to full scale
4 Lower limit deviation alert
5 Upper lower limit deviation alert
0 to full scale
6 Within-range alert
7 Upper limit input alert with standby Within the temperature measurement range of the set input range
( Page 96, Section 3.4.2 (12))8 Lower limit input alert with standby
9 Upper limit deviation alert with standby
(-(full scale)) to full scale
10 Lower limit deviation alert with standby
11 Upper lower limit deviation alert with standby 0 to full scale
12 Upper limit deviation alert with standby (second time)
(-(full scale)) to full scale
13 Lower limit deviation alert with standby (second time)
14
Upper lower limit deviation alert with standby (second
time)
0 to full scale
15 Upper limit deviation alert (using the set value (SV))
(-(full scale)) to full scale
16 Lower limit deviation alert (using the set value (SV))
17 Upper lower limit deviation alert (using the set value (SV))
0 to full scale
18 Within-range alert (using the set value (SV))