(5) Default setting registration instruction (Yn9)
Turning Default setting registration instruction (Yn9) on from off sets the data in the buffer memory areas back to
the default values according to control mode selection.
After the data writing is completed, Default value write completion flag (Xn9) turns on.
(a) When Setting/operation mode status (Xn1) is on (in operation mode)
Turning this instruction on from off does not set data back to the default value. Turn on this instruction when
Setting/operation mode status (Xn1) is off (in the setting mode).
(6) Setting change instruction (YnB)
Use this instruction to confirm the set value of the buffer memory (the buffer memory areas that can be set only in
the setting mode (Setting/operation mode status (Xn1): OFF)). ( Page 56, Section 3.3.3 (1))
(a) Reflection of set value
Even though the set values are written into the buffer memory, they cannot be reflected to the Q64TCN's
operation immediately. To confirm the set values, turn this instruction OFF ON OFF after the set values
are written into the buffer memory. Doing so lets the Q64TCN operate according to the setting in each buffer
memory area.
(7) CH PID control forced stop instruction (YnC to YnF)
Use this signal to temporarily stop PID control forcibly.
(a) Mode when PID control stops
The mode depends on the setting of CH Stop mode setting (Un\G33, Un\G65, Un\G97, Un\G129).
For details on CH Stop mode setting (Un\G33, Un\G65, Un\G97, Un\G129), refer to the following.
Page 103, Section 3.4.2 (13)