Mitsubishi Electronics Q64TCTTBWN Network Card User Manual


 
65
CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.1 Q64TCN buffer memory assignment list
95(5F
H
)
CH2
Automatic
backup setting
after auto tuning
of PID constants
Automatic
backup setting
after auto
tuning of PID
constants
Automatic
backup setting
after auto
tuning of PID
constants
*7
0R/W × ×
Page 128,
Section
3.4.2 (37)
96(60
H
)
CH3
Input range
*9
2(TT)
7(RT)
*5
R/W ×
Page 96,
Section
3.4.2 (12)
97(61
H
)
CH3
Stop mode
setting
Stop mode
setting
*6
Stop mode
setting
1R/W ×
Page 103,
Section
3.4.2 (13)
98(62
H
)
CH3
Set value (SV)
setting
Set value (SV)
setting
*6
Set value (SV)
setting
0R/W
Page 104,
Section
3.4.2 (14)
99(63
H
)
CH3
Proportional
band (P) setting
Heating
proportional
band (Ph)
setting
*6
Proportional
band (P)
setting
30 R/W ×
Page 105,
Section
3.4.2 (15)
100(64
H
)
CH3
Integral time (I)
setting
Integral time (I)
setting
*6
Integral time (I)
setting
240 R/W ×
Page 107,
Section
3.4.2 (16)
101(65
H
)
CH3
Derivative time
(D) setting
Derivative time
(D) setting
*6
Derivative time
(D) setting
60 R/W ×
Page 107,
Section
3.4.2 (17)
102(66
H
)
CH3 Alert set value 1
Alert set value
1
*6
Alert set value
1
0R/W
Page 108,
Section
3.4.2 (18)
103(67
H
)
CH3 Alert set value 2
Alert set value
2
*6
Alert set value
2
0R/W
104(68
H
)
CH3 Alert set value 3
Alert set value
3
*6
Alert set value
3
0R/W
105(69
H
)
CH3 Alert set value 4
Alert set value
4
*6
Alert set value
4
0R/W
106(6A
H
)
CH3
Upper limit
output limiter
Heating upper
limit output
limiter
*6
Upper limit
output limiter
1000 R/W ×
Page 110,
Section
3.4.2 (19)
107(6B
H
)
CH3
Lower limit
output limiter
System area
Lower limit
output limiter
0R/W ×
108(6C
H
)
CH3
Output variation
limiter setting
Output
variation limiter
setting
*6
Output
variation limiter
setting
0R/W ×
Page 112,
Section
3.4.2 (20)
109(6D
H
)
CH3 Sensor correction value setting 0 R/W ×
Page 113,
Section
3.4.2 (21)
110(6E
H
)
CH3
Adjustment
sensitivity (dead
band) setting
Adjustment
sensitivity
(dead band)
setting
*6
Adjustment
sensitivity
(dead band)
setting
5R/W ×
Page 113,
Section
3.4.2 (22)
111(6F
H
)
CH3
Control output
cycle setting
Heating control
output cycle
setting
*6
Control output
cycle setting
30 R/W ×
Page 114,
Section
3.4.2 (23)
112(70
H
)
CH3 Primary delay digital filter setting 0 R/W ×
Page 115,
Section
3.4.2 (24)
Address
(decimal
(hexadecimal))
Target
channel
or
current
sensor
(CT)
Setting contents
Default
value
*1
Read/
Write
*2
Automatic
setting
*3
E
2
PROM
write
availability
*4
Reference
Standard
control
Heating-
cooling
control
Mix control