CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(16)CH Integral time (I) setting (Un\G36, Un\G68, Un\G100, Un\G132)
Set integral time (I) to perform PID control.
(a) Setting range
The setting range is 0 to 3600 (0 to 3600s).
(b) In the P control or PD control
Set this setting to 0.
For details on control methods, refer to the following.
Page 166, Section 4.3
(c) Default value
The default values are set to 240 (240s) in all channels.
(17)CH Derivative time (D) setting (Un\G37, Un\G69, Un\G101, Un\G133)
Set derivative time (D) to perform PID control.
(a) Setting range
The setting range is 0 to 3600 (0 to 3600s).
(b) In the P control or PI control
Set this setting to 0.
For details on control methods, refer to the following.
Page 166, Section 4.3
(c) Default value
The default values are set to 60 (60s) in all channels.