Juniper Networks EX3200 Switch User Manual


 
Ensure that these environmental guidelines are followed:
The site must be as dust-free as possible, because dust can clog air intake vents and
filters, reducing the efficiency of the switch cooling system.
Maintain ambient airflow for normal switch operation. If the airflow is blocked or
restricted, or if the intake air is too warm, the switch might overheat, leading to the
switch temperature monitor shutting down the switch to protect the hardware
components.
Table 27 on page 91 provides the required environmental conditions for normal switch
operation.
Table 27: EX Series Switch Environmental Tolerances
ToleranceDescription
No performance degradation to10,000feet(3048 meters)Altitude
Normaloperationensuredinrelativehumidityrangeof10%through
85%, noncondensing
Relative humidity
EX2200,EX3200, EX4200,and EX4500 switches: Normal
operation ensuredin temperaturerangeof 32° F through113° F
(0°C through45° C)
EX8208 and EX8216 switches: Normal operation ensuredin
temperaturerangeof32°F through104°F (0°Cthrough40°C)
Temperature
ComplieswithZone4earthquakerequirementsasperGR-63,Issue
3.
Seismic
NOTE: InstallEX Series switches only in restrictedareas,such asdedicatedequipment
rooms and equipment closets, in accordance with Articles 110–16, 110–17,and 110–18
of the National Electrical Code, ANSI/NFPA70.
Related Topics Clearance Requirementsfor Airflow and Hardware MaintenanceforEX2200 Switches
Clearance Requirements for Airflow and Hardware Maintenance for EX3200 and
EX4200 Switches on page 96
ClearanceRequirementsforAirflowand HardwareMaintenanceforEX4500Switches
ClearanceRequirementsforAirflowandHardwareMaintenanceforanEX8208Switch
ClearanceRequirements forAirflow and Hardware Maintenanceforan EX8216 Switch
91Copyright©2010, JuniperNetworks, Inc.
Chapter4:SitePreparation