Juniper Networks EX3200 Switch User Manual


 
that the exhaust from other equipment does not blow into the intake vents of the
chassis.
Leave atleast 24in.(61cm) bothin frontof andbehind theEX3200 orEX4200 switch.
For service personnel to remove and install hardware components, you must leave
adequate space at the front and back of the switch. NEBS GR-63 recommends that
you allow at least 30 in. (76.2 cm) in front of the rack or cabinet and 24 in. (61 cm)
behind the rack or cabinet.
Figure 28: Airflow Through the EX3200 Switch Chassis
97Copyright©2010,Juniper Networks,Inc.
Chapter5:Mounting andClearanceRequirements