Juniper Networks EX3200 Switch User Manual


 
Table 29: Cabinet Requirements and Specifications for the Switch
GuidelinesCabinetRequirement
Youcanmounttheswitchinacabinetthatcontainsa19-in.
rackasdefined in Cabinets,Racks, Panels,and Associated
Equipment (documentnumber EIA-310–D)published by
theElectronicsIndustryAssociation(http://www.eia.org).
NOTE: The rack must meet the strengthrequirements to
support the weightof the switch.
Theminimum cabinetsize must be ableto accommodate
the maximumexternaldimensions of the switch.
Cabinetsize
Theouteredgesofthemountingbracketsextendthewidth
of the chassisto19 in. (48.3cm).
Theminimum totalclearanceinside the cabinet is 30 in.
(76.2cm)betweentheinsideofthefrontdoorandtheinside
of the reardoor.
Cabinetclearance
Whenyou mount the switchin a cabinet,ensure that
ventilationthrough the cabinetis sufficient toprevent
overheating.
Ensureadequate coolair supply todissipate the thermal
output of the switch or switches.
Ensurethat the cabinetallows the chassishot exhaustair
toexit the cabinetwithout recirculatingintothe switch.An
opencabinet(without a topordoors) thatemployshot air
exhaustextractionfrom the topallowsthe bestairflow
throughthe chassis.If the cabinet containsa topor doors,
perforationsintheseelementsassistwithremovingthehot
air exhaust.
Installtheswitchinthecabinetinawaythatmaximizesthe
open spaceon the side of the chassisthathas the hot air
exhaust.Thismaximizes the clearance forcritical airflow.
Route and dressall cables tominimize the blockageof
airflow toand from the chassis.
Ensurethatthespacingofrailsandadjacentcabinetsallows
forthe proper clearance around the switch and cabinet.
Acabinetlargerthantheminimumrequiredprovidesbetter
airflow and reduces the chanceof overheating.
Cabinetairflowrequirements
Related Topics Clearance Requirements for Airflow and Hardware Maintenance for EX3200 and
EX4200 Switches on page 96
Rack Requirements for EX3200 and EX4200 Switches on page 93
Mounting anEX3200 orEX4200Switchon TwoPostsin aRackorCabinetonpage122
Requirements for Mounting an EX3200 or EX4200 Switch on a Desktop or Wall
You can install the switchon a desktop or wall. When choosing a location, allowat least
6 in. (15.2 cm) of clearance between the front and back of the chassis and adjacent
equipment or walls.
95Copyright©2010, JuniperNetworks, Inc.
Chapter5:Mounting andClearanceRequirements