9-1
9. Specifications
9-1 Standard Specifications
(1) Three-phase 230V series
Nominal applied motor
[HP]
0.25 0.5 1 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150
Type
FRN[][][]G11S-2UX
F25 F50 001 002 003 005 007 010 015 020 025 030 040 050 060 075 100 125 -
Rated output
capacity (*1) [kVA]
0.6 1.2 2.0 3.2 4.4 6.8 10 13 18 24 29 35 46 58 72 86 113 138 -
Rated output
current (*2) [A]
1.5 3.0 5.0 8.0 11 17 25 33 46 59 74 87 115 145 180 215 283 346 -
Overload
capability
150% of rated output current for 1 min.
200% of rated output current for 0.5 s
150% of rated output current for 1 min.
180% of rated output current for 0.5 s
Starting torque 200% or more (under torque vector control) 180% or more (under torque vector control)
Braking torque
(*3) [%]
150% or more 100% or more Approx. 20% Approx. 10 to 15%
Braking time [s] 10 5 5 No limit
Braking duty
cycle [%ED]
10 5 3 5 3 2 3 2
No limit
G11
Mass [lbs (kg)] 4.9
(2.2)
4.9
(2.2)
5.5
(2.5)
8.4
(3.8)
8.4
(3.8)
8.4
(3.8)
13
(6.1)
13
(6.1)
22
(10)
22
(10)
23
(10.5)
23
(10.5)
64
(29)
79
(36)
97
(44)
101
(46)
154
(70)
254
(115)
-
Type
FRN[][][]P11S-2UX
- - - - - - 007 010 015 020 025 030 040 050 060 075 100 125 150
Rated capacity (*1)
[kVA]
- - - - - -
8.8 12 17 22 27 31 46 58 72 86 113 138 165
Rated output
current (*2) [A]
- - - - - -
22 29 42 55 67 78 115 145 180 215 283 346 415
Overload
capability
110% of rated output current for 1 min.
Starting torque 50% or more
Braking torque
(*3) [%]
Approx. 20% Approx. 10 to 15%
Braking time [s] No limit
Braking duty
cycle [%ED]
No limit
P11
Mass [lbs (kg)]
- - - - - -
13
(5.7)
13
(5.7)
13
(5.7)
22
(10)
22
(10)
23
(10.5)
64
(29)
64
(29)
79
(36)
97
(44)
101
(46)
154
(70)
254
(115)
Rated output
voltage (*4) [V]
3-phase, 200V/50Hz, 200V,220V,230V/60Hz
Output
ratings
Rated output
frequency [Hz]
50,60Hz
Phases, voltage,
frequency
3-phase, 200 to 230V, 50/60Hz
3-phase, 200 to 220V, 220 to 230V/50Hz
3-phase, 200 to 230V/60Hz
Voltage/frequency
variations
Voltage: +10% to -15% (Imbalance rate between phases: 2% or less (*6) , Frequency: +5% to -5%
Momentary voltage
dip capability (*7)
Operation will continue with 165V or more. If voltage drops below 165V, operation will continue for up to 15 ms.
If "Continuous operation" is selected, the output frequency will be lowered to withstand the load until normal voltage is resumed.
Input ratings
Required power
supply
capacity (*8)[kVA]
0.4 0.7 1.3 2.2 3.1 5.0 7.2 9.7 15 20 24 29 38 47 56 69 93 111 134