9-14
Data format [17] Type code
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Type Generation Series Voltage series
Code Type Generation Series Voltage series
1 - G11/P11 - -
2 G - - -
3 P - - 230V three phase
4 - - - 460V three phase
5 - - USA 575V three phase
6 - - - -
Data format [18] Code setting (14 figures)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Data 4 Data 3 Data 2 Data 1
Data format [19] Amperage value Decimal data (positive ):
Min. unit 0.01 inverter capacity is not more than 30HP
Min unit 0.01 for not less than 40HP
Example) If F11 (electronics thermal overload relay 1 level)107.0A (40HP)
107.0 X 10=1070=042E
H
If F11 (electronics thermal overload relay 1 level)=3.60A (1HP)
Since 3.60 X 100=360=0168
H
Data format [20] Transmission error code
Code Description Code Description
1 FC (function code) error 71 CRC error (no response)
2 Illegal address 72 Parity error (no response)
3 Illegal address (Data range error) 73 Other errors (no response)
-Framing error
-Overrun error
-Buffer full error
7 NAK
-Priority for comm.
-No privilege for writing error
-Forbidden writing error