5-20
This function switches the torque limit value set in
function codes F40 and F41, and E16 and E17 by an
external digital input signal.
Set value input signal
14
Torque limit
value selected
off
F40 DRV TRQ1
F41 BRK TRQ1
on
E16 DRV TRQ2
E17 BRK TRQ2
Setting range
DRV 20 to 200% ,999
BRK 0, 20 to 200% ,999
Motor operation can be switched from 50Hz commercial
power operation to inverter operation without stopping the
motor by switching the external digital input signal.
Set value
input signal
15
Function
offon
Inverter operation to line operation (50Hz)
onoff
Line operation to inverter operation (50Hz)
Motor operation can be switched from 60Hz commercial
power operation to inverter operation without stopping the
motor by switching the external digital input signal.
Set value
input signal
16
Function
offon
Inverter operation to line operation (60Hz)
onoff
Line operation to inverter operation (60Hz)
When the digital input signal goes off, 50 or 60 Hz is
output according to the set value input signal after the
restart waiting time following a momentary power failure
(function code H13). The motor is then directed to
inverter operation.
WARNING
- After the LU(Low Voltage) trip is occurred and reset it,
the inverter will automatically restart because the
operation command is kept by internal sequence.
Accident may result.
When an operation command is input (on), the output
frequency can be increased or decreased by an external
digital input signal.
The change ranges from 0 to maximum frequency.
Operation in the opposite direction of the operation
command is not allowed.
Combination of set
value input signals
18 17
Function selected
(when operation command is on)
off off
Holds the output frequency.
off on
Increases the output frequency
according to the acceleration time.
on off
Decreases the output frequency
according to the deceleration time.
on on
Holds the output frequency.
There are the two types of UP/DOWN operations as
shown below. Set the desired type by setting the
frequency (F01 or C30).
The data "8: UP/DOWN 1" is valid only when the Motor
2 is selected.
Frequency
setting
(F01 or C30)
Initial value
at power
input on
Operation command reentry
during deceleration
8
(UP/DOWN1)
0Hz
Operates at the frequency at reentry.
Frequency
FWD ON
(REV) OFF
9
(UP/DOWN2)
Previous
frequency
Returns to the frequency before
deceleration
Frequency
FWD ON
(REV) OFF
This function allows the data to be changed only when an
external signal is being input, thereby making it difficult to
change the data.
19
Function selected
off
Inhibit data changes.
on
Allow data changes.
Note:
If a terminal is set to value 19, the data becomes unable
to be changed. To change the data, turn on the terminal
and change the terminal setting to another number.
The PID control can be disabled by an external digital
input signal.
Set value
input signal
20
Function selected
off
Enable PID control.
on
Disable PID control
(frequency setting from keypad panel).
UP command [UP]/DOWN command [DOWN]
PID control cancel [Hz/PID]
Related function
H20H25
Switching operation between line and inverter (50Hz) [SW50]
Switching operation between line and inverter (60Hz) [SW60]
Torque limit 2/torque limit 1 [TL2/TL1]
Related function
F40F41
E16E17
Write enable for KEYPAD [WE-KP]
Related function
E01E09
(set value: 11, 35)
Related function
F01, C30