Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
6-2
6-2 Alarm Reset
To release the trip status, enter the reset command
by pressing the key on the keypad panel or
inputting signal from the terminal (RST) of the control
terminals after removing the cause of the trip. Since
the reset command is an edge operation, input a
command such as !!OFF-ON-OFF!! as shown in
Fig.6-2-1.
When releasing the trip status, set the operation
command to OFF. If the operation command is set
to ON, inverter will start operation after resetting.
WARNING
If the alarm reset is activated with the operation signal ON, the inverter will restart suddenly, which
may be dangerous. To ensure safety, disable the operating signal when releasing the trip status.
as accident may result.
Reset command OFF ON OFF
Keypad panel display
Normal
displa
y
Alarm display (Operable)
Alarm output
OFF
ON OFF
Fig.6-2-1
10ms o
r
Trip
RESET