Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
5-23
Some control and monitor signals can be selected and
output from terminals [Y1] to [Y5]. Terminals [Y1] to
[Y4] use transistor output; terminals[Y5A] and [Y5C]
use relay contacts.
Set
value
Output signal
0 Operating [RUN]
1 Frequency arrival [FAR]
2 Frequency detection [FDT1]
3 Stopping due to undervoltage [LV]
4 Torque polarity detection [B/D]
5 Torque limiting [TL]
6 Restarting after momentary power failure [IPF]
7 Overload early warning [OL1]
8 During keypad panel operation [KP]
9 Inverter stopping [STP]
10 Ready for operation [RDY]
11
Operation switching between line and inverter [SW88]
12
Operation switching between line and inverter [SW52-2]
13
Operation switching between line and inverter [SW52-1]
14 Motor 2 switching [SWM2]
15 Terminal AX function [AX]
16 Pattern operation stage change [TU]
17 Pattern operation cycle operation completed [TO]
18 Pattern operation stage number [STG1]
19 Pattern operation stage number [STG2]
20 Pattern operation stage number [STG4]
21 Alarm detail [AL1]
22 Alarm detail [AL2]
23 Alarm detail [AL4]
24 Alarm detail [AL8]
25 Cooling fan operating [FAN]
26 Retry function operating [TRY]
27
Universal DO [U-DO]
28 Heat sink overheat early warning [OH]
29
Synchronization completed by synchronous operation card [SY]
30 Life expectancy detection signal [LIFE]
31 2nd Freq. level detection [FDT2]
32 2nd OL level detection [OL2]
33 Terminal C1 off signal [C1OFF]
34
Speed existence signal [DNZS]
35
Speed agreement signal [DSAG]
36
PG error signal [PG-ABN]
37 Torque limiting (Signal with delay) [TL2]
Note: For output signals marked "
" are used for RS-485
communication, OPC-G11S-PG / PG2, PGA or
OPC-G11S-SY. Refer to each instruction manual.
"Running" means that the inverter is outputting a
frequency. “RUN” signal is output as when there is output
speed (frequency). When the DC injection brake
function is active, “RUN” signal is off.
See the explanation of function code E30 (frequency
arrival [detection width]).
See the explanation of function codes E31 and E32
(frequency detection).
If the undervoltage protective function activates, i.e.
when the main circuit DC voltage falls below the
undervoltage detection level, an ON signal is output. The
signal goes off when the voltage recovers and increases
above the detection level. The ON signal is retained
while the undervoltage protective function is activating.
Undervoltage detection level: 230V series: 200V, 460V
series: 400V.
This function determines the torque polarity calculated in
the inverter and outputs a signal indicating driving or
braking torque. An OFF signal is output for driving
torque; an ON signal is output for braking torque.
When the torque limiting activates, the stall prevention
function is automatically activated to change the output
frequency. The torque limiting signal is output to lighten
the load, and also used to display overload conditions on
the monitor device. This ON signal is output during the
current or torque is limited or power regeneration is
prevented.
Following a momentary power failure, this function
reports the start of the restart mode, the occurrence of
an automatic pull-in, and the completion of the recovery
operation.
Following a momentary power failure, an ON signal is
output when power is recovered and a synchronization
(pull-in) operation is performed. The signal goes off
when the frequency (before power failure) is recovered.
For 0Hz restart at power recovery, no signal is output
because synchronization ends when power is recovered.
The frequency is not recovered to the frequency before
the power failure occurrence.
Before the motor stops by the trip operation of an
electronic thermal O/L relay, this function outputs an ON
signal when the load reaches the overload early warning
level.
Either the electronic thermal O/L relay early warning or
output current overload early warning can be selected.
For setting procedure, see “E33 Overload early warning
(operation selection)”, and "E34 Overload early warning
(operation level)."
Note: This function is effective for motor 1 only.
An ON signal is output when operation command keys
( , and ) on the keypad panel can
be used (i.e., 0 set in "F02 Operation") to issue operation
and stop commands.
This signal is OFF when the function H30(Serial link) is
set to communication side.
E 2 0 Y 1 F U N C
E 2 1 Y 2 F U N C
E 2 2 Y 3 F U N C
E 2 3 Y 4 F U N C
E 2 4 Y 5 F U N C
Inverter running [RUN]
Undervoltage detection signal [LV]
Keypad operation mode [KP]
Frequency equivalence signal [FAR]
Frequency level detection [FDT1]
Torque polarity [B/D]
Torque limiting [TL]
Auto-restarting [IPF]
Overload early warning [OL1]
E20 Y1 terminal function
E24
Y5A and Y5C terminal function
FWD STOP REV