5-2
E:Extension Terminal Functions
Factory setting
Func
No.
NAME LCD Display Setting range Unit
Min.
Unit
-30HP 40HP-
Change
during op
User
Set value
Remark
E01 X1 terminal function E01 X1 FUNC 0 to 35 - - 0 NA
E02 X2 terminal function E02 X2 FUNC 1 NA
E03 X3 terminal function E03 X3 FUNC 2 NA
E04 X4 terminal function E04 X4 FUNC 3 NA
E05 X5 terminal function E05 X5 FUNC 4 NA
E06 X6 terminal function E06 X6 FUNC 5 NA
E07 X7 terminal function E07 X7 FUNC 6 NA
E08 X8 terminal function E08 X8 FUNC 7 NA
E09 X9 terminal function E09 X9 FUNC 8 NA
E10 Acceleration time 2 E10 ACC TIME2 s 0.01 6.00 20.00 A
E11 Deceleration time 2 E11 DEC TIME2 6.00 20.00 A
E12 Acceleration time 3 E12 ACC TIME3 6.00 20.00 A
E13 Deceleration time 3 E13 DEC TIME3 6.00 20.00 A
E14 Acceleration time 4 E14 ACC TIME4 6.00 20.00 A
E15 Deceleration time 4 E15 DEC TIME4
0.01 to 3600s
6.00 20.00 A
E16 Torque limiter 2 (Driving) E16 DRV TRQ 2 G11S: 20 to 200%, 999 % 1 999 A
P11S: 20 to 150%, 999
E17 (Braking) E17 BRK TRQ 2 G11S: 0%, 20 to 200%, 999 % 1 999 A
G11S: 0%, 20 to 150%, 999
E20 Y1 terminal function E20 Y1 FUNC 0 to 37 - - 0 NA
E21 Y2 terminal function E21 Y2 FUNC 1 NA
E22 Y3 terminal function E22 Y3 FUNC 2 NA
E23 Y4 terminal function E23 Y4 FUNC 7 NA
E24 Y5A, Y5C terminal func. E24 Y5 FUNC 10 NA
E25 Y5 RY operation mode E25 Y5RY MODE 0,1 - 1 0 NA
E30 FAR function (Hysteresis) E30 FAR HYSTR 0.0 to 10.0Hz Hz 0.1 2.5 A
E31 FDT function (Level) E31 FDT1 LEVEL G11S: 0 to 400Hz Hz 1 60 A
P11S: 0 to 120Hz
E32 signal (Hysteresis) E32 FDT1 HYSTR 0.0 to 30.0Hz Hz 0.1 1.0 A
E33 OL1 function(Mode select) E33 OL1 WARNING 0: Thermal calculation - - 0 A
1: Output current
E34 signal (Level) E34 OL1 LEVEL G11S: 5 to 200% A 0.01 Motor rated current A
P11S: 5 to 150%
E35 (Timer) E35 OL1 TIMER 0.0 to 60.0s s 0.1 10.0 A
E36 FDT2 function (Level) E36 FDT2 LEVEL G11S: 0 to 400Hz Hz 1 60 A
P11S: 0 to 120Hz
E37 OL2 function (Level) E37 OL2 LEVEL G11S: 5 to 200% A 0.01 Motor rated current A
G11S: 5 to 150%
E40 Display coefficient A E40 COEF A -999.00 to 999.00 - 0.01 0.01 A
E41 Display coefficient B E41 COEF B -999.00 to 999.00 - 0.01 0.00 A
E42 LED Display filter E42 DISPLAY FL 0.0 to 5.0s s 0.1 0.5 A
E43 LED Monitor (Function) E43 LED MNTR 0 to 12 - - 0 A
E44 (Display at STOP mode) E44 LED MNTR2 0, 1 - - 0 A
E45 LCD Monitor (Function) E45 LCD MNTR 0, 1 - - 0 A
E46 (Language) E46 LANGUAGE 0 to 5 - - 1 A
E47 (Contrast) E47 CONTRAST 0(soft) to 10(hard) - - 5 A
C:Control Functions of Frequency
Factory setting
Func
No.
NAME LCD Display Setting range Unit
Min.
Unit
-30HP 40HP-
Change
during op
User
Set value
Remark
C01 Jump frequency (Jump freq. 1) C01 JUMP Hz 1 Hz 1 0 A
C02 (Jump freq. 2) C02 JUMP Hz 2 0 A
C03 (Jump freq. 3) C03 JUMP Hz 3
G11S: 0 to 400Hz
P11S: 0 to 120Hz
0 A
C04 (Hysteresis) C04 JUMP HYSTR 0 to 30Hz Hz 1 3 A
C05 Multistep frequency (Freq. 1) C05 MULTI Hz-1 Hz 0.01 0.00 A
C06 setting (Freq. 2) C06 MULTI Hz-2 0.00 A
C07 (Freq. 3) C07 MULTI Hz-3 0.00 A
C08 (Freq. 4) C08 MULTI Hz-4 0.00 A
C09 (Freq. 5) C09 MULTI Hz-5 0.00 A
C10 (Freq. 6) C10 MULTI Hz-6 0.00 A
C11 (Freq. 7) C11 MULTI Hz-7 0.00 A
C12 (Freq. 8) C12 MULTI Hz-8 0.00 A
C13 (Freq. 9) C13 MULTI Hz-9 0.00 A
C14 (Freq. 10) C14 MULTI Hz-10 0.00 A
C15 (Freq. 11) C15 MULTI Hz-11 0.00 A
C16 (Freq. 12) C16 MULTI Hz-12 0.00 A
C17 (Freq. 13) C17 MULTI Hz-13 0.00 A
C18 (Freq. 14) C18 MULTI Hz-14 0.00 A
C19 (Freq. 15) C19 MULTI Hz-15
G11S: 0.00 to 400.00Hz
P11S: 0.00 to 120.00Hz
0.00 A