Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
5-1
5. Function select
5-1 Function select list
F:Fundamental Functions
Factory setting
Func
No.
NAME LCD Display Setting range Unit
Min.
Unit
-30HP 40HP-
Change
during op
User
Set value
Remark
F00 Data protection F00 DATA PRTC 0, 1 - - 0 NA
F01 Frequency command 1 F01 FREQ CMD 1 0 to 11 - - 0 NA
F02 Operation method F02 OPR METHOD 0 to 4 - - 0 NA
F03 Maximum frequency 1 F03 MAX Hz-1 G11S: 50 to 400Hz Hz 1 60 NA
P11S: 50 to 120Hz
F04 Base frequency 1 F04 BASE Hz-1 G11S: 25 to 400Hz Hz 1 60 NA
P11S: 25 to 120Hz
F05 Rated voltage 1 F05 RATED V-1 0V: (Output voltage V 1 230:(230V class) NA
(at Base frequency 1) proportinal to sorce voltage) 460:(460V class)
80 to 240V: (230V class)
320 to 480V: (460V class)
F06 Maximum voltage 1 F06 MAX V-1 80 to 240V: (230V class) V 1 230:(230V class) NA
(at Maximum frequency 1) 320 to 480V: (460V class) 460:(460V class)
F07 Acceleration time 1 F07 ACC TIME1 0.01 to 3600s s 0.01 6.0 20.0 A
F08 Deceleration time 1 F08 DEC TIME1
F09 Torque boost 1 F09 TRQ BOOST1 0.0, 0.1 to 20.0 - 0.1 G11S:2.0 A
P11S:2.0
F10 Electronic (Select) F10 ELCTRN OL1 0, 1, 2 - - 1 A
F11 thermal 1 (Level) F11 OL LEVEL1 INV rated current 20 to 135% A 0.01 Motor rated current A
F12 (Thermal time constant) F12 TIME CNST1 0.5 to 75.0 min min 0.1 5.0 10.0 A
F13 Electronic thermal overload relay F13 DBR OL G11 [Up to 10[HP]] - -
(for braking resistor) 0, 1, 2 1 A
[15[HP] and above ]
0
0
P11 [Up to 15[HP]]
0, 2
0
[020[HP] and above ]
0
0
F14 Restart mode after F14 RESTART 0 to 5 - - 0 NA
momentary power failure
F15 Frequency limiter (High) F15 H LIMITER G11S: 0 to 400Hz Hz 1 70 A
F16 (Low) F16 L LIMITER P11S: 0 to 120Hz 0 A
F17 Gain (for freq. set signal) F17 FREQ GAIN 0.0 to 200.0% % 0.1 100.0 A
F18 Bias frequency F18 FREQ BIAS G11S: -400.0 to +400.0Hz Hz 0.1 0.0 A
P11S: -120.0 to +120.0Hz
F20 DC brake (Starting freq.) F20 DC BRK Hz 0.0 to 60.0Hz Hz 0.1 0.0 A
F21 (Braking level) F21 DC BRK LVL G11S: 0 to 100% % 1 0 A
P11S: 0 to 80%
F22 (Braking time) F22 DC BRK t 0.0s(Inactive) s 0.1 0.0 A
0.1 to 30.0s
F23 Starting frequency (Freq.) F23 START Hz 0.1 to 60.0Hz Hz 0.1 0.5 NA
F24 (Holding time) F24 HOLDING t 0.0 to 10.0s s 0.1 0.0 NA
F25 Stop frequency F25 STOP Hz 0.1 to 60.0Hz Hz 0.1 0.2 NA
F26 Motor sound (Carrier freq.) F26 MTR SOUND 0.75 to 15kHz kHz 1 2 A
F27 (Sound tone) F27 SOUND TONE 0 to 3 - - 0 A
F30 FMA (Voltage adjust) F30 FMA V-ADJ 0 to 200% % 1 100 A
F31 (Function) F31 FMA FUNC 0 to 11 - - 0 A
F33 FMP (Pulse rate) F33 FMP PULSES 300 to 6000p/s (full scale) p/s 1 1440 A
F34 (Voltage adjust) F34 FMP V-ADJ 0%, 1 to 200% % 1 0 A
F35 (Function) F35 FMP FUNC 0 to 10 - - 0 A
F36 30RY operation mode F36 30RY MODE 0, 1 - - 0 NA
F40 Torque limiter 1 (Driving) F40 DRV TRQ 1 G11S: 20 to 200%, 999 % 1 999 A
P11S: 20 to 150%, 999
F41 (Braking) F41 BRK TRQ 1 G11S: 0%, 20 to 200%, 999 999 A
P11S: 0%, 20 to 150%, 999
F42 Torque vector control 1 F42 TRQVECTOR1 0, 1 - - 0 NA