Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
5-7
5-2 Function Explanation
Setting can be made so that a set value cannot be
changed by keypad panel operation.
Setting range 0 : The data can be changed.
1 : The data cannot be changed.
[Setting procedure ]
0 to 1: Press the and keys simultaneously
to change the value from 0 to 1, then press the
to validate the change.
1 to 0: Press the and keys simultaneously
to change the value from 1 to 0, then press the
key to validate the change.
This function selects the frequency
setting method.
0 : Setting by keypad panel operation ( key)
1 : Setting by voltage input (terminal [12 ](0 to +10V)
+ terminal [V2](0 to +10V) )
2: Setting by current input (terminal [C1] (4 to 20mA)).
3: Setting by voltage input + current input (terminal [12]
+ terminal [C1] ) (-10 to +10V + 4 to 20mA).
4: Reversible operation with polarity ( terminal [12]
(-10 to +10V))
5: Reversible operation with polarity ( terminal [12]
+[V2]+[V1](Option) (-10 to +10V))
6: Inverse mode operation
(terminal [12] +[V2] (+10V to 0 ))
7: Inverse mode operation
(terminal [C1] (20 to 4mA))
8: Setting by UP/DOWN control mode 1
(initial value = 0) (terminals
[
UP
]
and
[
DOWN
]
)
9: Setting by UP/DOWN control mode 2
(initial value =last final value)
(terminals [UP] and [DOWN])
See the function explanation of E01 to E09 for details.
10: Setting by pattern operation
See the function explanation C21 to C28 for details.
11: Setting by digital input or pulse train
* Optional. For details, see the instruction manual on options.
Set value:1,3
Set value:4,5
-10 0 +10 [V]
- Maximum frequency
Maximum frequency
Frequency setting value
A
nalog input terminal
[12] , [V2]
Inverse operation
(set value::6)
Forward operation
(set value: 1, 3, 4, 5)
0 4 20 [mA]
Maximum frequency
0
Frequency setting value
A
nalog input terminal
[C1]
Inverse operation
(set value: 7)
Forward operation
(set value: 2)
This function sets the operation command input
method.
Setting range 0: Key pad operation
( keys).
Press the for forward operation.
Press the for reverse operation.
Press the for deceleration to a stop.
Input from terminals [FWD] and [REV] is
ignored.
(LOCAL)
1: Terminal operation( key active)
2: Terminal operation( key inactive)
3: Terminal operation( key active)
with Fuji start software.
4: Terminal operation( key inactive)
with Fuji start software.
* - This function can only be changed when terminals FWD
and REV are open.
- REMOTE/LOCAL switching from the keypad panel
automatically changes the set value of this function.
- REMOTE/LOCAL can be changed by pressing the
key and key simultaneously.
F:
Fundamental function
F00 Data protection
F01 Frequency command 1
F02 Operation method
Related functions:
E01 to E09
(Set value 17,18)
Forward / Inverse operation
Related functions:
C21to C28
Related functions:
E01 to E09
(Set value 21)
F 0 0 D A T A P R T C
Related functions
E01 to E09
(Set values 19)
F 0 1 F R E Q C M D 1
Related functions
E01 to E09
(Set values 17,18)
C30
F 0 2 OPR M E T H O D
Related functions:
E01 to E09
(Set value 21)
FUNC
DATA
FUNC
DATA
FWD REV
STOP
STOP
STOP
FWD
REV
STOP
STOP
RESET
STOP
STOP
STOP
STOP