Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
4-13
4-3-13 Data copy
On the "Program menu" screen, select "9. Data Copy" to display the data copy read screen. A copy
operation is then performed in the following order;reading inverter function data, removing the keypad panel,
attaching the keypad panel to another inverter, and writing the data to the inverter.
The "verify" feature also makes it possible to compare and check differences in the data stored in the keypad
panel and the data stored in the inverter.
DATA copy screen
Mode (read mode)
60.00
RUN
PRG
PRG MENU
F/D
LED SHIFT
60.00
1.DATA SETTING
2.DATA CHECK
3.OPR MNTR
4.I/O CHECK
5.MAINTENANC
6.LOAD FCTR
7.ALM INF
8.ALM CAUSE
9.DATA COPY
Write data Read data
<DATA COPY>
-----
READ
<DATA COPY>
-----
READ

Reading
<DATA COPY>
040HP-4
READ
COMPLETE

Remove keypad panel
Data of inverter type
read by keypad panel
Read complete
60.00
RUN
PRG
PRG MENU
F/D
LED SHIFT
<DATA COPY>
040HP-4
READ
<DATA COPY>
040HP-4
WRITE
Mode (write mode)
<DATA COPY>
040HP-4
WRITE

Attach keypad panel,
Turn power ON.
Writing
<DATA COPY>
040HP-4
WRITE
COMPLETE

Write
complete
When WRITE to the type of the inverter (capacity,
voltage and series) is same as the inverter type in
copy origin, all of the function will be written. When
the type of the inverter is different, the function
except the following will be written. However, in both
cases, F00(Data protection), P02/A11(Motor capacity),
P04/A13 (Motor tuning), H03(Data initializing), H31(RS-485
address) and o26/AIO optional adjustment will NOT be
written.
- The function which will NOT be copied when different inverter type
FUNC. NAME FUNC. NAME
F03 Max. freq. 1 F26 Motor sound
F04 Base freq. 1 E33
OL function
(Mode select)
F05 Rated voltage 1 E34
OL function
(Level)
F06 Max. voltage 1 E35
OL function
(Timer)
F09 Torque boost 1 E37
OL2 function
(Level)
F10
Electronic
thermal 1
(Select)
H15
Auto-restart
(Holding DC
voltage)
F11
Electronic
thermal 1
(Level)
All of
"P"
code
Motor 1
F12
Electronic
thermal 1
(Thermal time
constant)
All of
"A"
code
Motor 2
F13 Electronic
thermal
overload relay
In addition, when WRITE from inverter ROM No. is new one to old
one, WRITE except F01(Freq. command 1) without ERROR display.
60.00
1.DATA SETTING
2.DATA CHECK
3.OPR MNTR
4.I/O CHECK
5.MAINTENANC
6.LOAD FCTR
7.ALM INF
8.ALM CAUSE
9.DATA COPY
Inverter type of data
stored by keypad panel
<DATA COPY>
040HP-4
WRITE
MEMORY ERROR

<DATA COPY>
040HP-4
WRITE
MEMORY ERROR
WRITE to the inverter with different
capacity, voltage and series.
FUNC
DATA
FUNC
DATA
FUNC
DATA
FUNC
DATA
FUNC
DATA
FUNC
DATA
PRG
PRG
PRG