Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
5-14
This function sets the upper and lower limits for the
setting frequency .
Setting range G11S: 0 to 400Hz
P11S: 0 to 120Hz
Upper limit value
Lower limit value
Lower limit value
Upper limit value
Set frequency
Set frequency
+ Maximum frequency
- Maximum frequency
+100%
-
100%
The inverter output starts with the start frequency when
operation begins, and stops with the stop frequency
when operation ends.
If the upper limit value is less than the lower limit value,
the upper limit value overrides the lower limit value.
When lower limit value is set, the inverter operates with
lower limit value at operation command is "ON" even
frequency command is zero(0Hz).
This function sets the rate of the set frequency value
to analog input.
Operation follows the figure below.
4 20mA
-10 0 +10[V]
Set frequency value
A
nalog input
+10V terminal 12
20mA terminal C1
200%
100%
50%
+Maximum
frequency
-Maximum
frequency
This function adds a bias frequency to the set
frequency value to analog input.
Setting range G11S: -400.0 to +400.0Hz
P11S: -120.0 to +120.0Hz
The operation follows the figure below.
When the bias frequency is higher than the maximum
frequency or lower than the - maximum frequency, it is
limited to the maximum or - maximum frequency.
4 20[mA]
-10 0 +10[V]
Set frequency value
A
nalog input
+10V terminal 12
20mA terminal C1
Bias frequency
(when positive)
Bias frequency
(when negative)
+Maximum
frequency
-Maximum
frequency
Reversible operation is valid if the function code
F01/C30 is set to "4" or "5" only.
This function is invalid if PID control is selected(H20 is
"1" or "2").
Starting frequency: This function sets the frequency
with which to start a DC injection brake to decelerate
the motor to a stop.
Setting range: 0 to 60Hz
Operation level: This function sets the output current
level when a DC injection brake is applied. Set a
percentage of inverter rated output current in 1% steps.
Setting range G11S: 0 to 100%
P11S: 0 to 80%
Time: This function sets the time of a DC injection
brake operation.
Setting range 0.0: Inactive
0.1 to 30.0 seconds
CAUTION
Do not use the inverter brake function for
mechanical holding.
Injury may result.
F20 DC brake (starting frequency)
DC brake (Braking level)
DC brake (Braking time)
F21
F22
F18 Bias frequency
Frequency limiter (High) F15
F16 Frequency limiter (Low)
F 1 8 FREQ B I A S
F 1 5 H L I M I T E R
F 1 6 L L I M I T E R
F 1 7 F R E Q G A I N
F 2 0 D C B R K H z
F 2 1 DC BR K L V L
F 2 2 DC BR K t
F17 Gain