Fuji Bikes 5000G11S/P11S Power Supply User Manual


 
4-9
4-3-9 Maintenance information
On the "Program menu" screen, select "5. Maintenance" to display information necessary for maintenance
and inspection. Use and to switch between the five screens of data.
60.00
60.00
60.00
1.DATA SETTING
2.DATA CHECK
3.OPR MNTR
4.I/O CHECK
TIME=xxxxxh
EDC= xxx
V
TMPI=xxxx
TMPF=xxxx
Cumulative operating time
DC link circuit voltage
Maximum temperature inside inverter
(Maximum value in hour units)
Maximum temperature of heat sink
(Maximum value in hour units)
60.00
60.00
Imax=x.xxA
CAP=xxx.x
%
60.00
Capacitor on PC
board
accumulation time
( ):Judgment level.
Cooling fan operating
time
( ):Judgment level.
Maximum current(ms)
(Maximum value in hour units)
Main capacitor capacity
No. of communication
errors:keypad panel
No. of communication
errors:RS-485
No. of communication
errors:option
60.00
INV=Hxxxx
KEYPAD=Kxxxxx
OPTION=Pxxxxx
ROM version: inverter
(40HP or more: H xxxxx
30HP or less:S xxxxx)
ROM version: keypad panel
ROM version: option
5.MAINTENANC
RUN
PRG
PRG MENU
F/D
LED SHIFT
NRK=xxxxx
NRR=xxxxx
NRO=xxxxx
TCAP=xxxxxh
(61000h)
TFAN=xxxxx
h
(25000h)
FWD
FUNC
DATA
PRG