Cisco ONS 15310-CL and Cisco ONS 15310-MA Troubleshooting Guide, R7.0
Chapter 2 Alarm Troubleshooting
2.7.52 DUP-SHELF-ID
Clear the DUP-NODENAME Alarm
Step 1 In node view, click the Provisioning > General tabs.
Step 2 In the Node Name/TID field, enter a unique name for the node.
Step 3 Click Apply.
Step 4 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447).
2.7.52 DUP-SHELF-ID
For information about this alarm or condition, refer to the “Alarm Troubleshooting” chapter in the
Cisco ONS 15454 DWDM Troubleshooting Guide. That guide discusses all DWDM alarms.
2.7.53 EHIBATVG
Default Severity: Major (MJ), Service-Affecting (SA)
SONET Logical Object: PWR
The Extreme High Voltage Battery alarm occurs in a –48 VDC environment when a battery lead input
voltage exceeds the extreme high power threshold. This threshold has a preset value of –56.5 VDC and
is not user-provisionable. The alarm is raised until the voltage remains under the threshold for
120 seconds.
Clear the EHIBATVG Alarm
Step 1 The problem is external to the ONS 15310-CL or ONS 15310-MA. Troubleshoot the power source
supplying the battery leads.
Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447) in order to report a Service-Affecting (SA)
problem.
2.7.54 ELWBATVG
Default Severity: Major (MJ), Service-Affecting (SA)
SONET Logical Object: PWR
The Extreme Low Voltage Battery alarm occurs in a –48 VDC environment when a battery lead input
voltage falls below the extreme low power threshold. This threshold has a preset value of –40.5 VDC
and is not user-provisionable. The alarm remains raised until the voltage remains over the threshold for
120 seconds.