Cisco Systems ONS 15310-MA Switch User Manual


 
2-52
Cisco ONS 15310-CL and Cisco ONS 15310-MA Troubleshooting Guide, R7.0
Chapter 2 Alarm Troubleshooting
2.7.59 EQPT-MISS
Step 3 If the CTC reset does not clear the alarm, complete the “Remove and Reinsert (Reseat) a Card”
procedure on page 2-154 for the reporting card.
Caution Always use the supplied electrostatic discharge wristband when working with a powered ONS 15310-CL
or ONS 15310-MA.
Step 4 If the physical reseat of the card fails to clear the alarm, complete the “Physically Replace a Card”
procedure on page 2-154 for the reporting card.
Note When you replace a card with the identical type of card, you do not need to make any changes
to the database.
Step 5 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447) in order to report a Service-Affecting (SA)
problem.
2.7.59 EQPT-MISS
Default Severity: Critical (CR), Service-Affecting (SA)
SONET Logical Object: FAN
The Replaceable Equipment or Unit Missing alarm is reported against the fan tray within the
ONS 15310-CL or ONS 15310-MA. It indicates that the fan is not operational, or that the
ONS 15310-MA fan tray is not present. For an ONS 15310-CL, this alarm is not user-serviceable. For
the ONS 15310-MA, complete the fan tray replacement procedure located in the Cisco ONS 15310-CL
and Cisco ONS 15310-MA Procedure Guide.
If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447) in order to report a Service-Affecting (SA)
problem.
2.7.60 ERFI-P-CONN
Default Severity: Not Reported (NR), Non-Service-Affecting (NSA)
SONET Logical Objects: STSMON, STSTRM
The Three-Bit (Enhanced) Remote Failure Indication (ERFI) Path Connectivity condition is triggered on
DS-1, DS-3, or VT circuits when the “UNEQ-P” alarm on page 2-142 and the “TIM-P” alarm on
page 2-139 are raised on the transmission signal.
Clear the ERFI-P-CONN Condition
Step 1 Complete the “Clear the UNEQ-P Alarm” procedure on page 2-142 and the “Clear the TIM-P Alarm”
procedure on page 2-139. This should clear the ERFI condition.