HEX DEC DESCRIPTION SOLUTION
008D
142
MAXIMUM CONNECTIONS EXCEEDED
You attempted to create more TCP client
connections than the 2572 will support.
You cannot create more than 8 TCP
Client connections.
0097 151 INVALID COMMAND
While attempting to execute a system
command, you specified an invalid command
number.
Correct the Command Number in the
Command Block.
009E 158 ALREADY BUSY
You attempted to send a command to a
function that was already busy executing a
previous command.
You can cause this error by using two
command slots to send commands to
the same connection number.
Dont do this.
009F 159 INVALID CONNECTION NUMBER
You specified a connection number that is out
of the valid range.
See the documentation for the
particular command block. Correct
the connection number as required.
00A5 165 INVALID SYSTEM COMMAND
Connection number 19200 (system) was
specified in the command block but the
command is not a valid system command.
Change the logical port to a valid
connection number or the command
number to a valid system command.
00A6 166 CONNECTION NOT ACTIVE
An attempt was made to send a command to
a connection number that has not been
created.
Note: you could receive this error if you
incorrectly entered the connection number in
the memory transfer command block.
Check the following for the Create
Socket Command:
1) Make sure that the command block
contains the correct data,
2) Ensure that the Command Slot
points to the proper command block,
3) Ensure that the Command Trigger
has been set.
4) Check for reported errors for the
Create Connection Command.
Check the Memory Transfer command
block for an incorrect connection
number entry.
00A7 167 DUPLICATE CONNECTION NUMBER
An attempt was made to create multiple
sockets with the same connection number.
or
You attempted to Start the 2572 Network
Server and it was already started.
or
You attempted to Start the 2572 Network
Server after a previous startup error had been
returned.
Ensure that all Create Socket
commands for serial ports use
different connection numbers.
Make sure you are not triggering the
Start Network Server Command more
than once or that you have not already
started the network server using the
dipswitch A
UTOSTART setting.
If an error occurs when starting the
network server, you must correct it
and reset the module.