IBM CTI 2572 Network Card User Manual


 
CTI 2572 Installation and Operation Guide
106
HEX DEC DESCRIPTION SOLUTION
23A3 9123 SBIT SELECTION ERROR
(Serial Ports Only)
The protocol manager was passed an invalid
number of stop bits. Valid stop bit values are
1 and 2.
See error code 23A0
23A4 9124 HSHAKE SELECTION ERROR
(Serial Ports Only)
The protocol manager was passed an invalid
handshake value. Valid handshake values
are 0- None, 1-Software, 2-Hardware
See error code 23A0
23AB 9131 SERVER ALREADY STARTED
The PLC logic attempted to start another copy
of the server on the same physical port.
If the error occurs while processing the Start
Network Server Command, the Network
Server was already started. Only one copy of
the server is required to service multiple
clients.
This is caused by a PLC logic error. It usually
occurs when you are triggering the command
more than once.
It also may occur when you AutoStart the
network server and also try to start the
network server from PLC logic.
23AC 9132 V MEMORY READ ERROR
The 2572 PLC server was unable to read the
requested V memory block.
This error code is for information only.
The remote device is requesting the 2572 to
read a V memory location that is out of the V
memory address boundary.
Correct the problem at the remote device or
re-configure the PLC to expand V memory
boundaries.
23AD 9133 V MEMORY WRITE ERROR
The 2572 PLC server was unable to write the
requested V memory block.
This error code is for information only.
The remote device is requesting the 2572 to
write a V memory location that is out of the V
memory address boundary.
Correct the problem at the remote device or
re-configure the PLC to expand V memory
boundaries.