CTI 2572 Installation and Operation Guide
109
HEX DEC DESCRIPTION SOLUTION
2470 9328
INVALID OPTION BIT
The option bit setting is invalid when
compared to the other parameters in the
command block.
Correct the option bit setting or change the
conflicting parameters.
If you are using TCP, you cannot set the IP
Address Location bit to 1.
2473 9331
BAD OR MISSING DELIMITER
The receiving device detected a bad or
missing delimiter in the command message
This error usually indicates a transient error in
the data link. You should retry the command.
If the receiving node is a computer simulating
a 2572 PLC server, ensure that the software
is correctly processing the message.
If the error persists contact CTI.
2474 9332
BAD BLOCK CHECK CHARACTER
The receiving device detected a block check
character error in the command message.
See error code 2473
2475 9333
INVALID TYPE
The receiving device reported an invalid TYPE
character in the message.
See error code 2473.
2476 9334
INVALID DATA CHARACTER
The receiving device reported an invalid data
character. Only characters 0-9 and A-F are
allowed.
See error code 2473.
2477 9335
ODD NUMBER OF CHARACTERS
The receiving device reported an odd number
of characters in the message. All CAMP
messages have an even number of
characters.
See error code 2473.
2478 9336
INVALID DEVICE CODE
The receiving device reported an invalid
device code in the message.
See error code 2473.
247A 9338
INVALID DEVICE CODE
The 2572 detected an invalid device code in
the response from the remote device
This error may result from a transient error in
the data link. You should retry the command.
If the problem persists, check the quality of
the data link.
If the remote node is a computer simulating a
2572 PLC server, ensure that the software is
correctly creating the response the response
message
247B 9339
BAD OR MISSING DELIMITER
The 2572 detected a missing delimiter in the
response message
See error code 247A.
247C 9340
BAD BLOCK CHECK CHARACTER
The 2572 found a bad block check character
in the response message.
See error code 247A.
247D 9341
INVALID TYPE
The 2572 detected an invalid TYPE character
in the message sent from the remote device.
See error code 247A.