IBM CTI 2572 Network Card User Manual


 
CTI 2572 Installation and Operation Guide
72
Start Consumer PLC B
Offset Description Hex Decimal
V100 Error Word 0000 0
V101 Command Code (Start DataShare Consumer) 2F03 12035
V102 Connection Number 4B29 19241
V103 Protocol Manager Number 002F 47
V104 Option Bits 0002 2
V105 Data ID (1 - 65565) 0001 1
V106 MSW: Destination V Memory Address 0000 0000
V107 LSW: Destination V Memory Address 07D0 2000
V108 Data Length in Words (1 - 512) 0064 100
V109 Starting Data Word in Data Block (1 - 512) 0001 1
V110-V115 Reserved, Set to 0 0000 0
Start Consumer PLC C
Offset Description Hex Decimal
V100 Error Word 0000 0
V101 Command Code (Start DataShare Consumer) 2F03 12035
V102 Connection Number 4B29 19241
V103 Protocol Manager Number 002F 47
V104 Option Bits 0002 2
V105 Data ID (1 - 65565) 0001 1
V106 MSW: Destination V Memory Address 0000 0000
V107 LSW: Destination V Memory Address 07D0 2000
V108 Data Length in Words (1 - 512) 0064 100
V109 Starting Data Word in Data Block (1 - 512) 0065 101
V110-V115 Reserved, Set to 0 0000 0
Start Consumer PLC D
Offset Description Hex Decimal
V100 Error Word 0000 0
V101 Command Code (Start DataShare Consumer) 2F03 12035
V102 Connection Number 4B29 19241
V103 Protocol Manager Number 002F 47
V104 Option Bits 0002 2
V105 Data ID (1 - 65565) 0001 1
V106 MSW: Destination V Memory Address 0000 0000
V107 LSW: Destination V Memory Address 07D0 2000
V108 Data Length in Words (1 - 512) 0064 100
V109 Starting Data Word in Data Block (1 - 512) 00C9 201
V110-V115 Reserved, Set to 0 0000 0