IBM CTI 2572 Network Card User Manual


 
CTI 2572 Installation and Operation Guide
99
HEX DEC DESCRIPTION SOLUTION
027A 634 INVALID DEVICE CODE
The 2572 detected an invalid device code in
the response from the remote device
This error may result from a transient error in
the data link. You should retry the command.
If the problem persists, check the quality of
the data link.
If the remote node is a computer simulating a
2572 PLC server, ensure that the software is
correctly creating the response the response
message
027B 635 BAD OR MISSING DELIMITER
The 2572 detected a missing delimiter in
the response message
See error code 027A.
027C 636 BAD BLOCK CHECK CHARACTER
The 2572 found a bad block check
character in the response message.
See error code 027A.
027D 637 INVALID TYPE
The 2572 detected an invalid TYPE
character in the message sent from the
remote device.
See error code 027A.
027E 638 INVALID DATA CHARACTER
The 2572 detected an invalid data character
in the message sent from the remote
device. Only characters 0-9 and A-F are
allowed.
See error code 027A.
027F 639 ODD NUMBER OF CHARACTERS
The 2572 detected an odd number of
characters in the message sent from the
remote device. All CAMP messages have
an even number of characters.
See error code 027A.
0280 640 UNKNOWN ERROR CHARACTER
The response contained an unknown error
character.
This error is probably caused by an
improperly programmed server node. If the
server is a PLC emulating a 2572 server,
review the code and correct as required. If the
server is another 2572, contact CTI.
0283 643 INVALID ADDRESS
The command contained a memory
address of 0.
The minimum CAMP address is 1. Enter the
correct value for the memory address.
0284 644 INCOMPLETE WRITE
The actual number of words written does
not match the requested number of words.
The actual number of words written is
contained in the response message from
the remote device.
This error is probably caused by an
improperly programmed server node. If the
server is a PLC emulating a 2572 server,
review the code and correct as required.
If the server is another 2572, contact CTI
0290 656 INVALID ADDRESS CLASS
The address class is not supported by the
server
See error 0284 above.