IBM CTI 2572 Network Card User Manual


 
CTI 2572 Installation and Operation Guide
75
Start Producer PLC C
Address Description Hex Decimal
V100 Error Word 0000 0
V101 Command Code (Start DataShare Producer)) 2F01 12033
V102 Connection Number 4B2B 19243
V103 Protocol Manager Number 002F 47
V104 Option Bits 0000 0
V105 Data ID (1 - 65565) 0003 3
V106 MSW: Source V Memory Address 0000 0
V107 LSW: Source V Memory Address 04B0 1200
V108 Length of Data in Words (1 - 512) 0064 100
V109 Trigger Option (1 = timer, 2 = logic, 3 = scan) 0003 3
V110 Timer Interval (when Offset 9 = 1)
Scan Interval (when Offset 9 = 3)
0001 2
V111-115 Reserved, Set to 0 0000 0
Consumer Command Blocks
Start Consumer PLC B & PLC C (Data Produced by PLC A)
Offset Description Hex Decimal
V100 Error Word 0000 0
V101 Command Code (Start DataShare Consumer) 2F03 12035
V102 Connection Number 4B29 19241
V103 Protocol Manager Number 002F 47
V104 Option Bits 0000 0
V105 Data ID (1 - 65565) 0001 1
V106 MSW: Destination V Memory Address 0000 0000
V107 LSW: Destination V Memory Address 03E8 1000
V108 Data Length in Words (1 - 512) 0064 100
V109 Starting Data Word in Data Block (1 - 512) 0001 1
V110-V115 Reserved, Set to 0 0000 0
Start Consumer PLC A & PLC C (Data Produced by PLC B)
Offset Description Hex Decimal
V100 Error Word 0000 0
V101 Command Code (Start DataShare Consumer) 2F03 12035
V102 Connection Number 4B2A 19242
V103 Protocol Manager Number 002F 47
V104 Option Bits 0000 0
V105 Data ID (1 - 65565) 0002 2
V106 MSW: Destination V Memory Address 0000 0000
V107 LSW: Destination V Memory Address 044C 1100
V108 Data Length in Words (1 - 512) 0064 100
V109 Starting Data Word in Data Block (1 - 512) 0001 1
V110-V115 Reserved, Set to 0 0000 0