CTI 2572 Installation and Operation Guide
59
Receive Timer used to break out of receive loop if continuous errors occur.
!C107 TMRF1---------+ C101
97 [-] [---------! !---------------------------------------( )
! ! !
! ! !
! ! P= 2.000 !
! ! !
!C107 ! !
[-] [---------! !
! +-------------+
Skips over logic section EXCEPT when executing “Receive Command” sequence.
! C12 SKP11
102 [-]/[---------------------------------------------------------------( )
!
C14 TRUE = Receive Command Enabled but not Executed. If “Cmd Busy” and “Cmd
Error” FALSE, set “Cmd Mode” and “Cmd Trigger” bits to execute Receive
Command in Coupled mode.
! C14 WX2.3 WX2.1 WY4.2
104 [-] [---]/[---]/[-------------------------------------------------*-( )
! !
! ! WY4.3
! +-( )
When “Cmd Busy” bit = TRUE, turn off C14. C14 FALSE = Receive Command has
been triggered.
!WX2.3 C14
117 [-] [---------------------------------------------------------------(RST )
!
If “Cmd Err” bit TRUE, it indicates error occurred when processing Recv Cmd.
Store error, set C108 TRUE (Error flag), and “Err Ack” bit.
! C14 WX2.1 MOVW2---------+ C108
123 [-]/[---] [---! !-------------------------------------*-(SET )
! ! A:V120 ! !
! ! B:V1405 ! ! WY4.1
! ! N=1 ! +-( )
! +-------------+
The Recv Cmd has completed (C14=FALSE and WX2.3=OFF). If no “Receive errors”
occurred, data is moved into storage buffer. If error occurred and Receive
Timer has expired (C101=TRUE), data is not transferred to storage buffer. If
X4 (Send Input)=TRUE, C12 (Recv Cmd Seq) is disabled, C15 (Send Cmd Enable)
is set, and C107 (Recv Timer) is reset.
! C14 WX2.3 WY4.3 C108 MOVW3---------+ X4 C12
137 [-]/[---]/[---]/[-*-]/[---! !-*-] [-------------------*-(RST )
! ! ! A:V1000 ! ! !
! ! ! B:V1700 ! ! ! C15
! ! ! N=25 ! ! [-(SET )
! ! +-------------+ ! !
! !C101 ! ! C107
! +-] [-------------------+ +-(RST )
!