230
www.gateway.com
Appendix A: Server Specifications
Environmental specifications
The following specifications identify maximum environmental conditions. At no time
should the server run under conditions which violate these specifications.
Variable Requirements
Temperature
Maximum rate of change: 18°F (10°C) per hour
Nonoperating: -40° to 158°F (-40° to 70°C)
Operating: 50° to 95°F (10° to 35°C); derated 0.9°F (0.5°C) for every
1,000 feet (305 meters)
Max BTU/hr.
5100
Altitude
-100 to 5000 feet (-30 to 1500 meters)
Humidity
Nonoperating: 95% (noncondensing) at 77° to 86° F (25° to 30° C)
Vibration
2.2 Grms, 10 minutes per axis on each of the three axis.
Shock
Operating: 2.0 g, 11 msec, ½ sine (100 pulses in each direction, on
each of three axes)
Non-Operating: Trapezoidal, 25 G, two drops on each of six faces
ΔV: 175 inches/sec on bottom face drop, 90 inches/sec on the other
five faces
8510702.book Page 230 Thursday, July 7, 2005 11:21 AM