Delta Electronics ASDA-AB Network Card User Manual


 
Chapter 7 Servo Parameters|ASDA-AB Series
7-82
Revision January 2009
P4 - 05 JOG JOG Operation Communication Addr.: 0405H
Default: 20 Related Section:
Applicable Control Mode: ALL Section 4.4.2
Unit: r/min
Range: 0~5000
Settings:
JOG operation command:
1. Operation Test
(1) Press the SET key to display the JOG speed. (The default value is 20 r/min).
(2) Press the UP or DOWN arrow keys to increase or decrease the desired JOG speed. (This
also can be undertaken by using the SHIFT key to move the cursor to the desired unit
column (the effected number will flash) then changed using the UP and DOWN arrow
keys).
(3) Press the SET when the desired JOG speed is displayed. The Servo Drive will display
"JOG".
(4) Press the UP or DOWN arrow keys to jog the motor either CCW or CW. The motor will
only rotation while the arrow key is activated.
(5) To change JOG speed again, press the MODE key. The servo Drive will display "P4 - 05".
Press the SET key and the JOG speed will displayed again. Refer back to #(2) and #(3) to
change speed.
2. DI Signal Control
Set the value of DI signal as JOGU and JOGD (refer to Table 7.A).
Users can perform JOG run forward and run reverse control.
3. Communication Control
To perform a JOG Operation via communication command, use communication address
0405H
(1) Enter 0 ~ 3000 for the desired JOG speed
(2) Enter 4998 to JOG in the CCW direction
(3) Enter 4999 to JOG in the CW direction
(4) Enter 5000 to stop the JOG operation
NOTE
1) If the communication write-in frequency is too high, please set P2-30 to 5.