CHAPTER 6 PCI Express card Hot Maintenance in Windows
6.5 Hot Replacement Procedure for iSCSI
146
C122-E175-01EN
6.5.1 Confirming the incorporation of a card with MPD
This section describes the procedure for confirming that a card has been incorporated with MPD.
1. Confirm physical location, segment number and bus number of target NIC.
Confirm the physical location, segment number and bus number with step 1 at 6.2.1 Replacement
procedure in 6.2 Common Hot Plugging Procedure for PCI Express cards.
Note
In case of multi-function card, there are some cards that have same segment number, same bus number,
and different function numbers.
In this case, please perform Step.2 to Step.7 of follows respectively.
2. Confirm target NIC in Device Manager.
Confirm NIC with step 2-a at 6.2.1 Replacement procedure in 6.2 Common Hot Plugging Procedure for
PCI Express cards.
3. Record IP address of target replaced NIC.
Open Command Prompt, command “ipconfig/all”, and record information that is necessary to reconfigure
IP address, subnet mask and so on of NIC after replacement.
4. Open iSCSI initiator.
5. Click the [Targets] tab in the [iSCSI Initiator Properties] window. One of the targets displayed in
[Discovered targets] is connected to the NIC to be replaced. If you know which target, select the target,
click the [Devices] button, and proceed to step 10.
If you do not know, select any target, click the [Properties] button, and proceed to step 7.