Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 94
3.2 Power Distribution and Power Conditioning Products
Table 33 Liebert Datawave
™
, Liebert FPC
™
, Liebert PPC
™
- Input and Holding - PMP, PM2 Options for
Liebert FPC and Liebert PPC
Controller Power Monitoring Panel - PMP, PM2 Options for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Status Points (View)
Voltage In X-Y — 40001 1 — V
Voltage In Y-Z — 40002 1 — V
Voltage In Z-X — 40003 1 — V
Voltage Out A-B — 40004 1 — V
Voltage Out B-C — 40005 1 — V
Voltage Out C-A — 40006 1 — V
Voltage Out A-N — 40007 1 — V
Voltage Out B-N — 40008 1 — V
Voltage Out C-N — 40009 1 — V
Current Out A — 40010 1 — A
Current Out B — 40011 1 — A
Current Out C — 40012 1 — A
Ground Current — 40013 1 10 A
Neutral Current — 40014 1 — A
kVA — 40015 1 — kVA
kW — 40016 1 — kW
Frequency — 40017 1 10 Hz
% Capacity A — 40018 1 — %
% Capacity B — 40019 1 — %
% Capacity C — 40020 1 — %
Power Factor — 40021 1 100 —
Kilowatt Hours — — 1 — —
THD Voltage X — — 1 — —
THD Voltage Y — — 1 — —
THD Voltage Z — — 1 — —
THD Current X — — 1 — —
THD Current Y — — 1 — —
THD Current Z — — 1 — —
K Factor Current X — — 1 — —
K Factor Current Y — — 1 — —
K Factor Current Z — — 1 — —
CREST Factor Current X — — 1 — —
CREST Factor Current Y — — 1 — —
CREST Factor Current Z — — 1 — —