Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 18
Service Required - Event Control 30317 40317 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Service Required - Event Type 30318 40318 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Shutdown - Loss Of Power - Event Control 30319 40319 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Shutdown - Loss Of Power - Event Type 30320 40320 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Smoke Detected - Event Control 30321 40321 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Smoke Detected - Event Type 30322 40322 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Water Under Floor - Event Control 30323 40323 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Water Under Floor - Event Type 30324 40324 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Compressor Lockout - Event Control 30325 40325 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Compressor Lockout - Event Type 30326 40326 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Clogged Air Filter - Event Control 30327 40327 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Clogged Air Filter - Event Type 30328 40328 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Loss of Air Blower - Event Control 30329 40329 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Loss of Air Blower - Event Type 30330 40330 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor High Head Pressure - Event
Control 1
30331 40331 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor High Head Pressure - Event
Control 2
30332 40332 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor High Head Pressure - Event
Type 1
30333 40333 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor High Head Pressure - Event
Type 2
30334 40334 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure - Event
Control 1
30335 40335 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure - Event
Control 2
30336 40336 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes