Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 116
Internal Comm Fail — 40290 1 — Bit 5
External Comm Fail — 40290 1 — Bit 6
CB1 Shunt Trip Fail — 40290 1 — Bit 7
CB2 Shunt Trip Fail — 40290 1 — Bit 8
CB6 Neutral Open — 40290 1 — Bit 9 (N/A to 4P)
Contactor Neutral Fail — 40290 1 — Bit 10 (N/A to 4P)
Heatsink Overtemp — 40290 1 — Bit 11
Equipment Overtemp — 40290 1 — Bit 12 (N/A to 4P)
Ambient Overtemp — 40290 1 — Bit 13 (N/A to 4P)
S1 Undervolts — 40290 1 — Bit 14
S1 Undervolts (RMS) — 40290 1 — Bit 15
S1 Overvolts — 40291 1 — Bit 0
S1 Over/Under Freq — 40291 1 — Bit 1
S1 Fail — 40291 1 — Bit 2
S2 Undervolts — 40291 1 — Bit 3
S2 Undervolts (RMS) — 40291 1 — Bit 4
S2 Overvolts — 40291 1 — Bit 5
S2 Over/Under Frequency — 40291 1 — Bit 6
S2 Fail — 40291 1 — Bit 7
S1 Overcurrent — 40291 1 — Bit 8
S2 Overcurrent — 40291 1 — Bit 9
S1 I-Peak — 40291 1 — Bit 10
S2 I-Peak — 40291 1 — Bit 11
Sources Out of Sync — 40291 1 — Bit 12
Load On Alternate Source — 40291 1 — Bit 13
Auto Retransfer Inhibit — 40291 1 — Bit 14
CB1 (S1) Open — 40292 1 — Bit 0
CB2 (S2) Open — 40292 1 — Bit 1
CB4 (S1 BYP) Closed — 40292 1 — Bit 2
CB5 (S2 BYP) Closed — 40292 1 — Bit 3
CB3 Output Bkr Open — 40292 1 — Bit 4
CB3A Output Bkr Open — 40292 1 — Bit 5
S1 Phase Rotation Error — 40292 1 — Bit 6
S2 Phase Rotation Error — 40292 1 — Bit 7
Transfer Inhibited — 40292 1 — Bit 8
Output Undervoltage — 40292 1 — Bit 9
History Logs Full — 40292 1 — Bit 10
Equipment Fan Fail — 40292 1 — Bit 11
Load Volt THD High — 40292 1 — Bit 12
Table 39 Liebert STS2
™
, Liebert STS2/PDU
™
- Input and Holding - STS2 (continued)
Controller STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units