Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 66
XD System 1 Secondary Fans
Fan State 31032 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31033 41033 1 —
0 = disabled
1 = automatic
2 = manual
XD System 2 Temperature Sensor 1
Remote Sensor Temperature 31039 — 1 10 Units : deg C
Remote Sensor Temperature 31040 — 1 10 Units : deg F
XD System 2 Temperature Sensor 2
Remote Sensor Temperature 31046 — 1 10 Units : deg C
Remote Sensor Temperature 31047 — 1 10 Units : deg F
XD System 2 Temperature Sensor 4
Remote Sensor Temperature 31060 — 1 10 Units : deg C
Remote Sensor Temperature 31061 — 1 10 Units : deg F
XD System 2 Secondary Fans
Fan State 31067 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31068 41068 1 —
0 = disabled
1 = automatic
2 = manual
XD System 3 Temperature Sensor 1
Remote Sensor Temperature 31074 — 1 10 Units : deg C
Remote Sensor Temperature 31075 — 1 10 Units : deg F
XD System 3 Temperature Sensor 2
Remote Sensor Temperature 31081 — 1 10 Units : deg C
Remote Sensor Temperature 31082 — 1 10 Units : deg F
XD System 3 Temperature Sensor 4
Remote Sensor Temperature 31095 — 1 10 Units : deg C
Remote Sensor Temperature 31096 — 1 10 Units : deg F
XD System 3 Secondary Fans
Fan State 31102 — 1 —
0 = off
1 = on
2 = economy
Fan Economy Mode 31103 41103 1 —
0 = disabled
1 = automatic
2 = manual
XD System 4 Temperature Sensor 1
Remote Sensor Temperature 31109 — 1 10 Units : deg C
Remote Sensor Temperature 31110 — 1 10 Units : deg F
XD System 4 Temperature Sensor 2
Remote Sensor Temperature 31116 — 1 10 Units : deg C
Remote Sensor Temperature 31117 — 1 10 Units : deg F
XD System 4 Temperature Sensor 4
Remote Sensor Temperature 31130 — 1 10 Units : deg C
Remote Sensor Temperature 31131 — 1 10 Units : deg F
Table 21 Liebert XDP
™
- Input and Holding (continued)
Data Label