Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Thermal Management Products
17 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Ext Condenser Pump High Water - Event
Control
30297 40297 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Condenser Pump High Water - Event
Type
30298 40298 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Standby Glycol Pump On - Event
Control
30299 40299 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Standby Glycol Pump On - Event Type 30300 40300 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Standby Unit On - Event Control 30301 40301 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Standby Unit On - Event Type 30302 40302 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Humidifier Lockout - Event Control 30303 40303 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Humidifier Lockout - Event Type 30304 40304 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Loss of Flow - Event Control 30305 40305 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Loss of Flow - Event Type 30306 40306 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Over Temperature - Event Control 30307 40307 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Over Temperature - Event Type 30308 40308 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Reheat Lockout - Event Control 30309 40309 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Ext Reheat Lockout - Event Type 30310 40310 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
High Power Shutdown - Event Control 30311 40311 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
High Power Shutdown - Event Type 30312 40312 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Humidifier Issue - Event Control 30313 40313 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Humidifier Issue - Event Type 30314 40314 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Master Unit Communication Lost - Event
Control
30315 40315 1
0 = disabled
1 = enabled
1, 2, 3, 4, 5, 6
Master Unit Communication Lost - Event
Type
30316 40316 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes