Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
221 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Compressors - Compressor 1
Compressor Hours Exceeded Binary_Value 77 5269_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor High Head Pressure Binary_Value 78 5270_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Low Suction Pressure Binary_Value 79 5271_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Short Cycle Binary_Value 80 5352_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Pump Down Issue Binary_Value 81 5146_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Thermal Overload Binary_Value 82 5272_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Dig Scroll Comp Discharge Temp
Sensor Issue
Binary_Value 83 5354_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Dig Scroll Comp Over Temp Binary_Value 84 5355_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Low Pressure Transducer
Issue
Binary_Value 85 5514_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor High Pressure
Transducer Issue
Binary_Value 86 5148_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Superheat Over
Threshold
Binary_Value 87 5604_1_1 RD Active on Alarm
2, 3, 4,
5, 6
Compressor Low Differential Pressure
Lockout
Binary_Value 88 5903_1_1 RD Active on Alarm 5
Compressors - Compressor 2
Compressor Hours Exceeded Binary_Value 97 5269_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor High Head Pressure Binary_Value 98 5270_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Low Suction Pressure Binary_Value 99 5271_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Short Cycle Binary_Value 100 5352_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Pump Down Issue Binary_Value 101 5146_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Thermal Overload Binary_Value 102 5272_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Dig Scroll Comp Discharge Temp
Sensor Issue
Binary_Value 103 5354_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Dig Scroll Comp Over Temp Binary_Value 104 5355_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Low Pressure Transducer
Issue
Binary_Value 105 5514_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor High Pressure
Transducer Issue
Binary_Value 106 5148_1_2 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Superheat Over
Threshold
Binary_Value 107 5604_1_2 RD Active on Alarm
2, 3, 4,
5, 6
Compressor Low Differential Pressure
Lockout
Binary_Value 108 5903_1_2 RD Active on Alarm 5
Table 76 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Binary Data (continued)
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes