Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 162
EcoModeSchedule 2
Schedule Operation State - ECO
Mode
30682 1
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode 30683 1
0 = stop
1 = start
SMS, 1+N,
SCC
Schedule Day of Week - ECO
Mode
30684 1
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
SMS, 1+N,
SCC
Schedule Hour - ECO Mode 30685 1 Units : hr
SMS, 1+N,
SCC
Schedule Minute - ECO Mode 30686 1 Units : min
SMS, 1+N,
SCC
EcoModeSchedule 16
Schedule Operation State - ECO
Mode
30794 1
0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode 30795 1
0 = stop
1 = start
SMS, 1+N,
SCC
Schedule Day of Week - ECO
Mode
30796 1
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
SMS, 1+N,
SCC
Schedule Hour - ECO Mode 30797 1 Units : hr
SMS, 1+N,
SCC
Schedule Minute - ECO Mode 30798 1 Units : min
SMS, 1+N,
SCC
Battery
Total Number of Battery Discharges 30821 1
SMS, 1+N,
N+1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 56 Liebert NXL
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types