Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - UPS Systems
357 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
ECO Mode Operation State This setting is used to enable or disable ECO Mode.
ECO Mode Suspended ECO Mode session is suspended.
EMO Shutdown An Emergency Module Off command has been detected.
Equipment Temperature Sensor Fail
One or more temperature sensors report a temperature outside of the range of
expected operation.
Excess ECO Suspends
Number of automatic suspensions has exceeded the ECO Mode - Maximum Auto
Suspensions setting.
Fuse Failure A summary event indicating one or more fuse failures
Inlet Air Over Temperature The inlet air exceeds the maximum temperature threshold
Inlet Air Temperature The temperature of the inlet air
Input Breaker Input breaker
Input Contact 01 The external input contact 1
Input Contact 02 The external input contact 2
Input Contact 03 The external input contact 3
Input Contact 04 The external input contact 4
Input Contact 05 The external input contact 5
Input Contact 06 The external input contact 6
Input Contact 07 The external input contact 7
Input Contact 08 The external input contact 8
Input Contact 09 The external input contact 9
Input Contact 10 The external input contact 10
Input Contact 11 The external input contact 11
Input Contact 12 The external input contact 12
Input Contact 13 The external input contact 13
Input Contact 14 The external input contact 14
Input Contact 15 The external input contact 15
Input Contact 16 The external input contact 16
Input Filter Cycle Lock
The input filter disconnect is open due to exceeding the maximum number of
cycles.
Input Isolation Transformer Input isolation transformer
Input Qualification Status input qualification status
Intelligent Parallel Maximum Time in
Standby
The maximum time a module can be in standby mode due to Intelligent Paralleling.
Intelligent Parallel Minimum
Redundancy
This is the minimum Number of Redundant Modules that the system will allow
before bringing one or more modules back to normal operation and terminating
Intelligent Paralleling.
Intelligent Parallel Operation State This setting is used to enable or disable Intelligent Paralleling.
Internal Bypass Breaker Internal bypass breaker
Internal Communications Failure
The control has detected a communication failure of a component on the internal
communication bus
Inverter Failure Inverter failure - inverter output is off
Inverter Inhibit - External Restart of the inverter is inhibited by an external signal
Inverter On/Off State inverter on/off state
Inverter Output Qualification Status inverter output qualification status
Inverter Overload Phase A Inverter is operating with an overload on phase A
Inverter Overload Phase B Inverter is operating with an overload on phase B
Table 113 Liebert NXL
- 50 Hz, CE version (Models 48 and 49)—Glossary
Data Label Data Description