Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 232
Calculated Next Maintenance
Month
Analog_Value 284 4868_1 RD
1, 2, 3,
4, 5, 6
Calculated Next Maintenance
Year
Analog_Value 285 4869_1 RD
1, 2, 3,
4, 5, 6
Hot Water / Hot Gas Valve Open
Position
Analog_Value 286 5380_1 RD Units: %
1, 2, 3,
4, 5, 6
Reheat Utilization Analog_Value 287 5080_1 RD Units: %
1, 2, 3,
4, 5, 6
Humidifier Utilization Analog_Value 288 5081_1 RD Units: %
1, 2, 3,
4, 5, 6
Dehumidifier Utilization Analog_Value 289 5079_1 RD Units: %
1, 2, 3,
4, 5, 6
Cooling Capacity Analog_Value 290 5490_1 RD Units: %
2, 3, 4,
5, 6
Adjusted Humidity Analog_Value 291 5606_1 RD Units: % RH
2, 3, 4,
5, 6
Return Dew Point Analog_Value 292 5004_1 RD Units: deg C
2, 3, 4,
5, 6
Return Dew Point Analog_Value 10292 5004_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Actual Air Temperature Set
Point
Analog_Value 293 5607_1 RD Units: deg C
2, 3, 4,
5, 6
Actual Air Temperature Set
Point
Analog_Value 10293 5607_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Actual Humidity Set Point Analog_Value 294 5608_1 RD Units: % RH
2, 3, 4,
5, 6
Dew Point Set Point Analog_Value 295 5575_1 RW Units: deg C
2, 3, 4,
5, 6
Dew Point Set Point Analog_Value 10295 5575_1_deg_F RW Units: deg F
2, 3, 4,
5, 6
Cooling Control Temperature Analog_Value 296 5615_1 RD Units: deg C
2, 3, 4,
5, 6
Cooling Control Temperature Analog_Value 10296 5615_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Fan Speed Control Temperature Analog_Value 297 5616_1 RD Units: deg C
2, 3, 4,
5, 6
Fan Speed Control Temperature Analog_Value 10297 5616_1_deg_F RD Units: deg F
2, 3, 4,
5, 6
Unit Cooling Load Analog_Value 298 5904_1 RD Units: kW 6
Time
System Date and Time Analog_Value 300 4293_1 RW
1, 2, 3,
4, 5, 6
Remote Sensors
Remote Sensor Over Temp
Threshold
Analog_Value 312 5589_1 RW Units: deg C
2, 3, 4,
5, 6
Remote Sensor Over Temp
Threshold
Analog_Value 10312 5589_1_deg_F RW Units: deg F
2, 3, 4,
5, 6
Remote Sensor Under Temp
Threshold
Analog_Value 313 5590_1 RW Units: deg C
2, 3, 4,
5, 6
Remote Sensor Under Temp
Threshold
Analog_Value 10313 5590_1_deg_F RW Units: deg F
2, 3, 4,
5, 6
Table 78 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Analog Data (continued)
Data Label Object Type
Instanc
eObject Name
Acces
sNotes
Extra
Notes