Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - UPS Systems
329 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
System Status MultiState_Value 91 4123_1 RD
1 = Normal Operation
2 = StartUp
3 = Normal with
Warning
4 = Normal with Alarm
5 =
AbNormalOperation
SMS, 1+N,
N+1, SCC
UPS Output Source MultiState_Value 92 4872_1 RD
1 = Other
2 = off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
SMS, 1+N,
N+1, SCC
Peak kW Demand Period MultiState_Value 93 5795_1 RD
1 = Hourly
2 = Daily
3 = Weekly
4 = Monthly
5 = Yearl
SMS, 1+N,
N+1, SCC
Ratings
Input Isolation Transformer MultiState_Value 104 4266_1 RD
1 = Not Installed
2 = Installed
SMS, 1+N,
N
Device Status
Backfeed Breaker MultiState_Value 115 4764_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N,
SCC
SBS Load Disconnect MultiState_Value 116 4765_1 RD
1 = Open
2 = Close
3 = Not Installed
Obsolete
Input Breaker (CB1/RIB) MultiState_Value 117 4766_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N,
N+1
Trap Filter Disconnect MultiState_Value 118 4767_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N,
N+1
Output Breaker (CB2/IOB) MultiState_Value 119 4768_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N,
N+1
Internal Bypass Breaker
(CB3)
MultiState_Value 120 4769_1 RD
1 = Open
2 = Close
3 = Not Installed
Obsolete
Bypass Isolation Breaker
(BIB)
MultiState_Value 121 4770_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N
Rectifier Feed Breaker (RFB) MultiState_Value 122 4771_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS
Maintenance Bypass Breaker
(MBB)
MultiState_Value 123 4772_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N,
SCC
Maintenance Isolation
Breaker (MIB)
MultiState_Value 124 4773_1 RD
1 = Open
2 = Close
3 = Not Installed
SMS, 1+N,
SCC
Output Series Static Switch MultiState_Value 125 4774_1 RD
1 = off
2 = on
3 = Not Installed
LEU/LAP
only
Table 108 Liebert NXL
- 60Hz, UL version (Model 40) - Multistate Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type