Modbus 485 and Modbus IP Protocols - Thermal Management Products
75 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 23 Liebert DS
™
and Liebert PeX
™
- Status and Coil
Controller Liebert iCOM
™
v3
Data Description
Status Coil
Number
of Bits Scale Notes / Units
Sleep on Monday 10001 1 1 — —
Sleep on Tuesday 10002 2 1 — —
Sleep on Wednesday 10003 3 1 — —
Sleep on Thursday 10004 4 1 — —
Sleep on Friday 10005 5 1 — —
Sleep on Saturday 10006 6 1 — —
Sleep on Sunday 10007 7 1 — —
Supply Limit Enable 10008 8 1 — —
Reheat Lockout 10009 9 1 — —
Humidifier Lockout 10010 10 1 — —
Temperature Indication
1
10011 11 1 — —
Timer Mode Type 10012 12 1 — —
Minimum Chilled Water Temp Enable 10013 13 1 — —
Std. Sensor Alarms Enable 10019 19 1 — —
Sensor A Alarms Enable 10020 20 1 — —
Compressor Lockout 10021 21 1 — —
VSD Fan speed 10022 22 1 — —
Unit Control — 25 1 — —
Reset Alarm — 26 1 — —
Acknowledge Alarm — 27 1 — —
Reset Total Run Hours Fan Motor — 28 1 — —
Reset Comp1Run Hour — 29 1 — —
Reset Comp2Run Hour — 30 1 — —
Reset Humidifier Run Hour — 31 1 — —
Reset Dehumidifier Run Hour — 32 1 — —
Reset CW/FC Run Hour — 33 1 — —
Reset E-Heater1RunHour — 34 1 — —
Reset E-heater2RunHour — 35 1 — —
Reset E-heater3 Run Hour — 36 1 — —
Reset HG/HW Run Hour — 37 1 — —
Fan On 10025 — 1 — —
Cool On 10026 — 1 — —
Free Cool On 10027 — 1 — —
Hot Water On 10028 — 1 — —
Electrical Heater On 10029 — 1 — —
Humidification On 10030 — 1 — —
Dehumidification On 10031 — 1 — —
Audible Alarm On 10032 — 1 — —
Reserved 10033 — 1 — —
Main Fan Overload 10034 — 1 — —
Loss of Airflow 10035 — 1 — —
Loss of Flow 10036 — 1 — —
Comp 1 High Pressure 10037 — 1 — —
Comp 1 Low Pressure 10038 — 1 — —