Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 238
System Event Configuration
Customer Input 1 - Event
Control
MultiState_Value 126 4718_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Customer Input 1 - Event Type MultiState_Value 127 4719_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Customer Input 2 - Event
Control
MultiState_Value 128 5098_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Customer Input 2 - Event Type MultiState_Value 129 5099_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Customer Input 3 - Event
Control
MultiState_Value 130 5100_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Customer Input 3 - Event Type MultiState_Value 131 5101_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Customer Input 4 - Event
Control
MultiState_Value 132 5102_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Customer Input 4 - Event Type MultiState_Value 133 5103_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Free Cooling Lockout -
Event Control
MultiState_Value 134 5389_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Free Cooling Lockout -
Event Type
MultiState_Value 135 5390_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Condenser Pump High
Water - Event Control
MultiState_Value 136 5122_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Condenser Pump High
Water - Event Type
MultiState_Value 137 5123_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Standby Glycol Pump On -
Event Control
MultiState_Value 138 5129_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Standby Glycol Pump On -
Event Type
MultiState_Value 139 5130_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Standby Unit On - Event
Control
MultiState_Value 140 5391_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Standby Unit On - Event
Type
MultiState_Value 141 5392_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Humidifier Lockout - Event
Control
MultiState_Value 142 5086_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Humidifier Lockout - Event
Type
MultiState_Value 143 5087_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Ext Loss of Flow - Event Control MultiState_Value 144 5082_1 RW
1 = disabled
2 = enabled
1, 2, 3,
4, 5, 6
Ext Loss of Flow - Event Type MultiState_Value 145 5083_1 RW
1 = Message
2 = Warning
3 = Alarm
1, 2, 3,
4, 5, 6
Table 80 Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
,
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
- Multistate Data (continued)
Data Label Object Type Instance Object Name Access Notes
Extra
Notes