Emerson BACNET IP Power Supply User Manual


 
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 350
Configuration Description MultiState_Value 91 4751_1 RD
1 = Single
Module System
33
2 = Single
Module System
34
3 = Single
Module System
44
4 = 1+1 33
5 = 1+1 34
6 = 1+1 44
7 = 1+N 33
8 = 1+N 34
9 = 1+N 44
10 = N+1 33
11 = N+1 34
12 = N+1 44
13 = SCC w/
Continuous Duty
SS 33
14 = SCC w/
Continuous Duty
SS 44
15 = SCC w/
Momentary Duty
SS
16 = Main Static
Switch
UPS System Output Source MultiState_Value 92 4307_1 RD
1 = None
2 = Inverter
3 = Bypass
System Input Power Source MultiState_Value 93 4318_1 RD
1 = None
2 = Utility (mains)
3 = Generator
System Status MultiState_Value 94 4123_1 RD
1 = Normal
Operation
2 = StartUp
3 = Normal with
Warning
4 = Normal with
Alarm
5 = Abnormal
Operation
UPS Output Source MultiState_Value 95 4872_1 RD
1 = Other
2 = Off
3 = Normal
4 = Bypass
5 = Battery
6 = Booster
7 = Reducer
System Fan Status MultiState_Value 96 4326_1 RD
1 = Unknown
2 = Normal
3 = Failure
System Fan Redundant Status MultiState_Value 97 4327_1 RD
1 = Unknown
2 = Redundancy
Available
3 = Loss of
Redundancy
System Fan Capacity Status MultiState_Value 98 4328_1 RD
1 = Unknown
2 = Normal
3 = Failure
Table 112 Liebert NXL
- 50 Hz, CE version (Models 48 and 49)—Multistate Data
Data Label
Object Type Instance Object Name Access Notes