BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 286
Circuit 2 Low Suction Pressure - Event
Type
Multistate_Value 114 4698_1 RW
1 = Message
2 = Warning
3 = Alarm
Hot Gas
Hot Gas Solenoid Valve 1 Position Multistate_Value 125 4701_1 RD
1 = Closed
2 = Open
Hot Gas Solenoid Valve 2 Position Multistate_Value 126 4702_1 RD
1 = Closed
2 = Open
XD System 1
Communication Status Multistate_Value 137 5486_1 RD
1 = Connected
2 = Not Connected
Fan On/Off Control Multistate_Value 138 5487_1 RW 1 = Off / 2 = On
Primary Fan Group State Multistate_Value 139 5509_1 RD
1 = Off / 2 = On
3 = Economy
Fan Button Control Multistate_Value 140 5488_1 RW
1 = Enabled
2 = Disabled
Visual ID Control Multistate_Value 141 5489_1 RW
1 = Disabled
2 = Enabled
Ext System Condensation Detected - Event
Control
Multistate_Value 142 5493_1 RW
1 = Disabled
2 = Enabled
Ext System Condensation Detected - Event Type Multistate_Value 143 5494_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Fan Issue - Event Control Multistate_Value 144 5496_1 RW
1 = Disabled
2 = Enabled
Ext Fan Issue - Event Type Multistate_Value 145 5497_1 RW
1 = Message
2 = Warning
3 = Alarm
Sensor Issue - Event Control Multistate_Value 146 5498_1 RW
1 = Disabled
2 = Enabled
Sensor Issue - Event Type Multistate_Value 147 5499_1 RW
1 = Message
2 = Warning
3 = Alarm
Ext Remote Shutdown - Event Control Multistate_Value 148 5501_1 RW
1 = Disabled
2 = Enabled
Ext Remote Shutdown - Event Type Multistate_Value 149 5502_1 RW
1 = Message
2 = Warning
3 = Alarm
XD System 1 Secondary Fans 1
Fan State Multistate_Value 160 5510_1_1 RD
1 = Off / 2 = On
3 = Economy
Fan Economy Mode Multistate_Value 161 5511_1_1 RW
1 = Disabled
2 = Automatic
3 = Manual
XD System 2
Communication Status Multistate_Value 172 5486_2 RD
1 = Connected
2 = Not Connected
Fan On/Off Control Multistate_Value 173 5487_2 RW 1 = Off / 2 = On
Primary Fan Group State Multistate_Value 174 5509_2 RD
1 = Off / 2 = On
3 = Economy
Table 94 Liebert XDP
™
, Liebert XDC
™
- Multistate Data (continued)
Controller Liebert iCOM
®
v4
Data Label
Object Type Instance
Object
Name Access Notes