Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 212
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
39123-39152 1
Scale
: x /
10
Units : deg F
Ordinal Position of String
String 1 - 32
33522-33553 1
Index of Parent Battery
String 1 - 32
33554-33585 1
Cell Entity (Cells 1 – 320)
Cell Voltage
Cell 1 - 320
33586-33905 1
Scale
: x /
1000
Units : VDC
Cell Temperature
Cell 1 - 320
33906-34225 1
Scale
: x /
10
Units : deg C
Cell Temperature
Cell 1 - 320
34226-34545 1
Scale
: x /
10
Units : deg F
Internal Resistance Value
Cell 1 - 320
34546-34865 1 Units : microOhm
Intercell Resistance Value
Cell 1 - 320
34866-35185 1 Units : microOhm
Cell Voltage Low Threshold
Cell 1 - 320
35186-35505 1
Scale
: x /
1000
Units : VDC
Cell Voltage High Threshold
Cell 1 - 320
35506-35825 1
Scale
: x /
1000
Units : VDC
Cell Temperature Low Threshold
Cell 1 - 320
35826-36145 1
Scale
: x /
10
Units : deg C
Cell Temperature Low Threshold
Cell 1 - 320
36146-36465 1
Scale
: x /
10
Units : deg F
Cell Temperature High Threshold
Cell 1 - 320
36466-36785 1
Scale
: x /
10
Units : deg C
Cell Temperature High Threshold
Cell 1 - 320
36786-37105 1
Scale
: x /
10
Units : deg F
Internal Resistance Low Threshold
Cell 1 - 320
37106-37425 1 Units : microOhm
Internal Resistance High Threshold
Cell 1 - 320
37426-37745 1 Units : microOhm
Intercell Resistance High Threshold
Cell 1 - 320
37746-38065 1 Units : microOhm
Ordinal Position of Cell
Cell 1 - 320
38066-38385 1
Index of Parent String
Cell 1 - 320
38386-38705 1
Index of Parent Battery
Cell 1 - 320
38706-39025 1
Cell Entity (Cells 321 – 360)
Cell Voltage
Cell 321 - 360
39155-39194 1
Scale
: x /
1000
Units : VDC
Table 75 Alber
®
BDSU
- Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of