Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
105 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Panel 2 Position 2
Breaker position 31607 1
Branch Current Phase 1 31608 1 10 A AC
Branch Current Phase 2 31609 1 10 A AC
Branch Current Phase 3 31610 1 10 A AC
Branch Output Power (kW) 31611 1 1000 kW
Output kW-Hrs 31612 2 1000 kWH
Branch Output Power Factor 31614 1 100
Branch Output Percent Load 31615 1 %
Panel 2 Position 84
Breaker position 32591 1
Branch Current Phase 1 32592 1 10 A AC
Branch Current Phase 2 32593 1 10 A AC
Branch Current Phase 3 32594 1 10 A AC
Branch Output Power (kW) 32595 1 1000 kW
Output kW-Hrs 32596 2 1000 kWH
Branch Output Power Factor 32598 1 100
Branch Output Percent Load 32599 1 %
Panel 3 Position 1
Breaker position 32603 1
Branch Current Phase 1 32604 1 10 A AC
Branch Current Phase 2 32605 1 10 A AC
Branch Current Phase 3 32606 1 10 A AC
Branch Output Power (kW) 32607 1 1000 kW
Output kW-Hrs 32608 2 1000 kWH
Branch Output Power Factor 32610 1 100
Branch Output Percent Load 32611 1 %
Panel 3 Position 2
Breaker position 32615 1
Branch Current Phase 1 32616 1 10 A AC
Branch Current Phase 2 32617 1 10 A AC
Branch Current Phase 3 32618 1 10 A AC
Branch Output Power (kW) 32619 1 1000 kW
Output kW-Hrs 32620 2 1000 kWH
Branch Output Power Factor 32622 1 100
Branch Output Percent Load 32623 1 %
Table 36 Liebert FDC
, Liebert FPC
, Liebert RDC
, Liebert RX
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units