Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 158
Sum of MMS Output RMS Currents
for Phase B
30512 1 Units : A AC 1+N, SCC
Sum of MMS Output RMS Currents
for Phase C
30513 1 Units : A AC 1+N, SCC
MMS Output Frequency 30514 1 10 Units : Hz 1+N, SCC
MMS Output Power 30515 1 Units : kW 1+N, SCC
MMS Output Apparent Power 30516 1 Units : kVA 1+N, SCC
MMS Output Power Factor
Phase A
30517 1 100 1+N, SCC
MMS Output Power Factor
Phase B
30518 1 100 1+N, SCC
MMS Output Power Factor
Phase C
30519 1 100 1+N, SCC
MMS Output Pct Power Phase A 30520 1 Units : % 1+N, SCC
MMS Output Pct Power Phase B 30521 1 Units : % 1+N, SCC
MMS Output Pct Power Phase C 30522 1 Units : % 1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase A
30523 1 Units : % 1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase B
30524 1 Units : % 1+N, SCC
MMS Output Pct Apparent Pwr
(kVA) Phase C
30525 1 Units : % 1+N, SCC
Number of Redundant Modules 30526 1 1+N, SCC
MMS Module Number 30527 1 1+N, SCC
Number of Modules in an MMS 30528 1 1+N, SCC
Module Output Breaker for
Module 1 (MOB1)
30529 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 2 (MOB2)
30530 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 3 (MOB3)
30531 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 4 (MOB4)
30532 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 5 (MOB5)
30533 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 6 (MOB6)
30534 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 7 (MOB7)
30535 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Module Output Breaker for
Module 8 (MOB8)
30536 1
0 = Open
1 = Close
2 = Not Installed
1+N, SCC
Table 56 Liebert NXL
- 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types