Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
103 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Panel Main Voltage Vy THD 30514 — 1 10 % THD
Panel Main Voltage Vz THD 30515 — 1 10 % THD
Panel Main Current Ix THD 30516 — 1 10 % THD
Panel Main Current Iy THD 30517 — 1 10 % THD
Panel Main Current Iz THD 30518 — 1 10 % THD
Panel Main Current Ix Crest Factor 30519 — 1 10 —
Panel Main Current Iy Crest Factor 30520 — 1 10 —
Panel Main Current Iz Crest Factor 30521 — 1 10 —
Panel 4
Columns of Breakers 30556 — 1 — —
Number of Breakers 30557 — 1 — —
Panel Main Voltage X-Y 30558 — 1 — VAC
Panel Main Voltage Y-Z 30559 — 1 — VAC
Panel Main Voltage Z-X 30560 — 1 — VAC
Panel Main Voltage X-N 30561 — 1 — VAC
Panel Main Voltage Y-N 30562 — 1 — VAC
Panel Main Voltage Z-N 30563 — 1 — VAC
Panel Main Current Ix 30564 — 1 — A AC
Panel Main Current Iy 30565 — 1 — A AC
Panel Main Current Iz 30566 — 1 — A AC
Panel Main Neutral Current 30567 — 1 — A AC
Panel Main Ground Current 30568 — 1 10 A AC
Panel Main Output Power (kVA) 30569 — 1 — kVA
Panel Main Output Power (kW) 30570 — 1 — kW
Panel Main Output kW-Hrs 30571 40571 2 10 kWH
Panel Main Output Power Factor 30573 — 1 100 —
Panel Main Output Percent Load 30574 — 1 - %
Panel Main Voltage Vx THD 30575 — 1 10 % THD
Panel Main Voltage Vy THD 30576 — 1 10 % THD
Panel Main Voltage Vz THD 30577 — 1 10 % THD
Panel Main Current Ix THD 30578 — 1 10 % THD
Panel Main Current Iy THD 30579 — 1 10 % THD
Panel Main Current Iz THD 30580 — 1 10 % THD
Panel Main Current Ix Crest Factor 30581 — 1 10 —
Panel Main Current Iy Crest Factor 30582 — 1 10 —
Panel Main Current Iz Crest Factor 30583 — 1 10 —
Table 36 Liebert FDC
™
, Liebert FPC
™
, Liebert RDC
™
, Liebert RX
™
- Input and Holding (continued)
Controller Liebert iCOM
®
v4
Liebert Products Liebert FDC, Liebert FPC, Liebert RDC, Liebert RX
Available Points
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units