Emerson BACNET IP Power Supply User Manual


 
Modbus 485 and Modbus IP Protocols - UPS Systems
191 Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Table 62 Liebert PowerSure
Interactive (before July 2008) - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 Bits 8 - 11
Number of SubModules 30009 40009 1 -
Load Circuit Present 30013 40013 1
There are 16 possible Load Circuits. Each bit
represents 1 load circuit. Load Circuit 1 is bit
0, Load Circuit 2 is bit 1 and so on. If the bit
is 1, then the Load Circuit is supported.
Nominal Power Rating 30021 40021 2 VA
Nominal Input Voltage 30027 40027 1 V
Nominal Output Voltage 30028 40028 1 V
Nominal Input Current 30030 40030 1 A
Nominal Input Frequency 30031 40031 1 10 Hz
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100
Nominal Battery Voltage 30034 40034 1 V
Auto Restart Delay 30051 40051 1 Seconds
Device Low Battery Time 30053 40053 1 Minutes
Load (Apparent Power) 30102 2 VA
Load / Capacity 30106 1 %
Input Frequency 30107 1 10 Hz
Output Frequency 30108 1 10 Hz
Battery Charge Status 30112 1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage 30113 1 V
Battery Time Remaining 30115 1 Minutes
Battery Charge Percentage 30116 1 %
Battery Test Result 30130 1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
7 - Inhibited
Input Voltage L1 30153 1 V
Output Voltage L1 30163 1 V
Output Current L1 30164 1 A
Input Maximum Voltage L1 30180 1 V
Input Minimum Voltage L1 30181 1 V
Output Maximum Voltage L1 30182 1 V
Output Minimum Voltage L1 30183 1 V
Black Out Count 30301 1
Brown Out Count 30302 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.