BACnet Communications - Thermal Management Products
Liebert
®
IntelliSlot
®
Modbus/BACnet IP 220
4.2 Thermal Management Products
Table 76 Liebert Challenger 3000
™
, Liebert Challenger ITR
™
, Liebert CW
™
, Liebert Deluxe System/3
™
,
Liebert DS
™
, Liebert DSE
™
, Liebert HPM
™
, Liebert PeX
™
- Binary Data
Controller Liebert iCOM
®
v4
Data Description
Object Type Instance
Object
Name Access Notes
Extra
Notes
Air - Supply Air
Supply Air Over Temperature Binary_Value 1 5015_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Supply Air Under Temperature Binary_Value 2 5019_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Supply Air Sensor Issue Binary_Value 3 5026_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Air - Return Air
Return Air Over Temperature Binary_Value 14 5023_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Return Air Under Temperature Binary_Value 15 5335_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Return Air Sensor Issue Binary_Value 16 5147_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Air - External Sensors
Ext Air Sensor A Over Temperature Binary_Value 27 4601_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Air Sensor A Under Temperature Binary_Value 28 4608_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Air Sensor A Issue Binary_Value 29 4618_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ambient Air Sensor Issue Binary_Value 30 5573_1_1 RD Active on Alarm
2, 3, 4,
5, 6
Humidity
High Return Humidity Binary_Value 41 5034_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Low Return Humidity Binary_Value 42 5036_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Dew Point Over Temperature Binary_Value 43 5578_1 RD Active on Alarm
2, 3, 4,
5, 6
Dew Point Under Temperature Binary_Value 44 5579_1 RD Active on Alarm
2, 3, 4,
5, 6
Return Humidity Sensor Issue Binary_Value 45 5902_1 RD Active on Alarm 5, 6
Humidity - External Sensors
Ext Air Sensor A High Humidity Binary_Value 53 5349_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Air Sensor A Low Humidity Binary_Value 54 5351_1_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Ext Dew Point Over Temperature Binary_Value 55 4615_1_1 RD Active on Alarm
2, 3, 4,
5, 6
Ext Dew Point Under Temperature Binary_Value 56 5577_1_1 RD Active on Alarm
2, 3, 4,
5, 6
Compressors
Ext Compressor Lockout Binary_Value 65 5067_1 RD Active on Alarm
1, 2, 3,
4, 5, 6
Compressor Capacity Reduced Binary_Value 66 5513_1 RD Active on Alarm
1, 2, 3,
4, 5, 6